Chapter 4 Explanation of Functions

Data Description

Reference

item

Page

53

MJA: Major failure

Major failure signal

4-70

54 WCO
55 WCOI
56 WCO

Window comparators function

4-71

4.2.59 Intelligent output terminal a/b (NO/NC) selection

The intelligent output terminal a/b (NO/NC) selection function
allows you to specify a-contact or b-contact output for each of
the intelligent output terminals [11] to [15] and the alarm relay
terminal.
The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal
is used for relay output.

Item Function

code

Data

Description

00

a-contact (NO)

Terminal active state

C031 to C035

01

b-contact (NC)

00

a-contact (NO)

Alarm relay active state

C036

01

b-contact (NC)


- An a-contact turns on the output signal when closed and turns it off when opened.
- A b-contact turns on the output signal when opened and turns it off when closed.

(1) Specifications of intelligent output terminals [11] to [15]
Intelligent output terminals [11] to [15] have the following specifications:

15 CM2 …

… 11



Setting of C031 to C035

Power supply

Output signal

ON

ON

OFF

00

(a-contact)

OFF

ON

ON

OFF

01

(b-contact)

OFF


(2) Specifications of alarm relay terminal
The alarm relay terminal uses a normally-closed (NC) contact that operates as described below.

AL0 AL1 AL2





Example of operation as an alarm output terminal

Output terminal state

Setting

of C036

Power
supply

Inverter

status

AL1-AL0 AL2-AL0

Error Closed Open

ON

Normal Open Closed

00

OFF

- Open

Closed

Error Open

Closed

ON

Normal Closed Open

01

(default)

OFF

- Open

Closed

4 -

61

C031 to C035: Terminal [11] to [15] active state
C036: Alarm relay active state

Related code

Electric characteristics

(Between each terminal and CM2)
Voltage drop when turned on: 4 V or less
Allowable maximum voltage: 27 VDC
Allowable maximum current: 50 mA

Inside the
inverter

Resistance load

Inductive load

Maximum contact

capacity

250 VAC, 2 A

30 VDC,

3

A

250 VAC, 2 A

30 VDC, 8 A

AL1-AL0

Minimum contact

capacity

100 V AC, 10 mA

5 VDC, 100 mA

Maximum contact

capacity

250 VAC, 1A

30 VDC, 1A

250 VAC, 0.2 A

30 VDC, 0.2 A

AL2-AL0

Minimum contact

capacity

100 VAC, 10 mA

5 VDC, 100 mA

Inside the
inverter