Chapter 4 Explanation of Functions

4.2.21 Jump frequency function

A063: Jump (center) frequency setting 1
A064: Jump (hysteresis) frequency width
setting 1
A065: Jump (center) frequency setting 2
A066: Jump (hysteresis) frequency width
setting 2
A067: Jump (center) frequency setting 3
A068: Jump (hysteresis) frequency width
setting 3

Related code

The jump frequency function allows you to operate the inverter so
that it avoids the resonant frequency of the machine driven by the
same.
Since the inverter avoids the motor operation with a constant output
frequency within the specified range of the frequencies to jump when
the jump frequency function is enabled, you cannot set any inverter
output frequency within the specified range of the frequencies to
jump.
Note that, while the inverter is accelerating or decelerating the motor, the inverter output frequency
changes continuously according to the set acceleration/deceleration time.
You can set up to three frequencies to jump.

Item

Function code

Range of data

Description

Jump (center) frequency
settings, 1st/2nd/3rd settings

A063/A065/
A067

0.00 to 400.0 (Hz) (*1)

Setting of the center frequency of the
frequency range to be jumped

Jump (hysteresis) frequency
width settings, 1st/2nd/3rd
settings

A064/A066/
A068

0.00 to 10.00(Hz)

Setting of the half bandwidth of the
frequency range to be jumped

*1 Setting of 0 Hz disables the jump frequency function.

4 -

25










4.2.22 Acceleration stop frequency setting

A063

A065

A067

A064

A064

A066

A066

A068

A068

Output fr

Frequency command

equency

A069: Acceleration stop frequency setting
A070: Acceleration stop time frequency
setting

Related code

The acceleration stop frequency setting function allows you to make
the inverter wait, upon starting the motor, until the slipping of the
motor becomes less when the load on the motor causes a large
moment of inertia.
Use this function if the inverter has tripped because of overcurrent when starting the motor.
This function can operate with every acceleration pattern, regardless of the setting of the acceleration
curve selection (A097).

Item

Function code

Range of data

Description

Acceleration stop frequency
setting

A069

0.00 to 400.0(Hz)

Setting of the frequency at which to
stop acceleration

Acceleration stop time
frequency setting

A070

0.0 to 60.0(s)

Setting of the length of time to stop
acceleration


A070

A069

Output fr

ncy command

equency

Freque