Chapter 4 Explanation of Functions

(Example 1

4 - 1

3




















4.2.12 Frequency operation function

The frequency operation function allows you to use the result of an
arithmetic operation on two frequency commands as the actual
frequency command or PID feedback data.
To use the operation result as the actual frequency command,
specify "10" for the frequency source setting (A001).
To use the operation result as the PID feedback data, specify "10" for the PV source setting (A076).

Item Function

code

Data

Description

00

Digital operator (A020/A220/A320)

(01)

Control on the digital operator
(Valid only when the OPE-SR is connected)

02

Input via the O terminal

03

Input via the OI terminal

04

Input via the RS485 terminal

05

Input from option board 1

06

Input from option board 2

Operation-target frequency
selection 1 and 2

A141/A142

07

Input of pulse train

00

Addition: (A141) + (A142)

01

Subtraction: (A141) - (A142)

Operator selection for
frequency operation

A143

02

Multiplication: (A141) x (A142)

Frequency source setting

A001

10

Output of operation result

PV source setting

A076

10

Output of operation result


Note 1: The [1] (up) and [2] (down) keys of the digital operator are ineffective when the frequency

operation function is enabled. Also, the frequency displayed by the output frequency monitoring
(d001), Scaled output frequency monitoring (d007), or output frequency setting (F001) cannot be
changed with key operations.

Note 2: The settings of "A141" and "A142" can be the same.

f

O

f

O2

f

OI

+f

O2

0

AT

f

OI

0

0

f

O

+ f

O2

FW

FW

AT

f

OI

0

0

0

f

O

f

O2

f

O

+ f

O2

f

OI

+f

O2

) When
peration

eversible

y

erminal

iliary

y

rminal

y

Forward

operation

Forward

operation

Reverse

operation

(Example 1) When
the motor operation
is reversible

Main frequency
command via the OI
or O terminal

Auxiliary
frequency
command via
the O2 terminal

Actual frequency
command

the motor o
is not r

Main frequenc
command via the OI
or O t

Aux
frequenc
command via
the O2 te

Actual frequenc
command

A141: Operation-target frequency selection 1
A142: Operation-target frequency selection 2
A143: Operator selection
A001: Frequency source setting
A076: PV source setting

Related code