Chapter 4 Explanation of Functions

4 - 12

6

(vii) 06 command: This command reads a specified setting item from the inverter.
- Transmission frame
Frame format

STX Station

No.

Command

Parameter

BCC

CR

Description

Data

size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target
inverter

2 bytes

01 to 32

Command

Command to be transmitted

2 bytes

06

Parameter

Data parameter number

4 bytes

See Note 12.

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."
See Item (3) of this section.

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

Note 12: The parameters that can be specified for reading are F002 to F004, A001 to A153, b001 to

b132, C001 to C159, H003 to H073, and P001 to P131. (To read the F001 parameter, use the
01 command.)

- Response frame
Positive response:
Frame format

STX Station

No. ACK

Data

BCC

CR

Description

Data

size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target
inverter

2 bytes

01 to 32

ACK

Control code (acknowledgement)

1 byte

ACK (0x06)

Data

Data to be sent (decimal ASCII
code)

8 bytes

See Note 13.

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."
See Item (3) of this section.

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

Note 13: When the read parameter is an selection item, the Data part contains the code data

corresponding to the selection.

The code data corresponding to "H003" or "H203" (motor capacity selection) is as follows:

Code

data

00 01 02 03 04 05 06 07 08 09 10

Japan or U.S.A. mode

(b085 = 00 or 02)

0.2 kW

-

0.4

-

0.75

-

1.5

2.2

-

3.7

-

EU mode (b085 = 01)

0.2 kW

0.37

-

0.55

0.75

1.1 1.5 2.2 3.0

-

4.0

Code

data

11 12 13 14 15 16 17 18 19 20 21

Japan or U.S.A. mode

(b085 = 00 or 02)

5.5

kW

7.5 11 15 18.5 22 30 37 45 55 75

EU mode (b085 = 01)

5.5 kW

7.5

11

15

18.5

22

30

37

45

55

75

For the value contained in the Data part when the read parameter is a numerical item, see the list of
function codes.
(Example) When the setting of the acceleration (1) time (F002) is 30.00 seconds, the Data part contains
"3000".
Negative response: See Item (2)-(ii) of this section.