Coil No.

Item

R/W

Setting

0035h

LOG2 (logical operation result 2)

R

1: ON, 0: OFF

0036h

LOG3 (logical operation result 3)

R

1: ON, 0: OFF

0037h

LOG4 (logical operation result 4)

R

1: ON, 0: OFF

0038h

LOG5 (logical operation result 5)

R

1: ON, 0: OFF

0039h

LOG6 (logical operation result 6)

R

1: ON, 0: OFF

003Ah

WAC (capacitor life warning)

R

1: ON, 0: OFF

003Bh

WAF (cooling-fan speed drop)

R

1: ON, 0: OFF

003Ch

FR (starting contact signal)

R

1: ON, 0: OFF

003Dh

OHF (heat sink overheat warning)

R

1: ON, 0: OFF

003Eh LOC

(low-current

indication signal)

R

1: ON, 0: OFF

003Fh

M01 (general output 1)

R

1: ON, 0: OFF

0040h

M02 (general output 2)

R

1: ON, 0: OFF

0041h

M03 (general output 3)

R

1: ON, 0: OFF

0042h

M04 (general output 4)

R

1: ON, 0: OFF

0043h

M05 (general output 5)

R

1: ON, 0: OFF

0044h

M06 (general output 6)

R

1: ON, 0: OFF

0045h

IRDY (inverter ready)

R

1: ON, 0: OFF

0046h

FWR (forward rotation)

R

1: ON, 0: OFF

0047h

RVR (reverse rotation)

R

1: ON, 0: OFF

0048h

MJA (major failure)

R

1: ON, 0: OFF

0049h

Data writing in progress

R

1: Writing in progress, 0: Normal status

004Ah

CRC error

R

1: Error detected, 0: No error (*2)

004Bh

Overrun

R

1: Error detected, 0: No error (*2)

004Ch

Framing error

R

1: Error detected, 0: No error (*2)

004Dh

Parity error

R

1: Error detected, 0: No error (*2)

004Eh

Sum check error

R

1: Error detected, 0: No error (*2)

004Fh (reserved)

0050h

WCO (window comparator O)

R

1: ON, 0:FF

0051h

WCO (window comparator OI)

R

1: ON, 0:FF

0052h

WCO (window comparator O2)

R

1: ON, 0:FF


*1 Normally, this coil is turned on when the corresponding intelligent input terminal on the control circuit

terminal block is turned on or the coil itself is set to on. In this regard, the operation of the intelligent
input terminal has priority over the operation of the coil. If disconnection of the communication train
has disabled the master system from turning off the coil, turn the corresponding intelligent input
terminal on the control circuit block on and off. This operation turns off the coil.

*2 Communication error data is retained until an error reset command is input. (The data can be reset

during the inverter operation.)