Chapter 8 List of Data Settings

8 - 7

Default

Code

Function name

Monitored data or setting

_FF _FEF

_FUF

Setting

during

operation

(allowed or

not)

Change

during

operation

(allowed or

not)

Page

b034

Run/power-on warning time

0. to 9999. (0 to 99990), 1000 to 6553 (10000 to 655300) (hr)

0.

¯

{

4-64

b035 Rotational

direction

restriction

00 (enabling both forward and reverse rotations), 01 (enabling
only forward rotation), 02 (enabling only reverse rotation)

00

¯

¯

4-7

b036

Reduced voltage start selection

0 (minimum reduced voltage start time) to 255 (maximum
reduced voltage start time)

6

¯

{

4-42

b037

Function code display restriction

00 (full display), 01 (function-specific display), 02 (user setting),
03 (data comparison display), 04 (basic display)

04

¯

{

4-76

b038 Initial-screen

selection

00 (screen displayed when the STR key was pressed last), 01
(d001), 02 (d002), 03 (d003), 04 (d007), 05 (F001)

01

¯

{

4-78

Oth

e

rs

b039

Automatic user-parameter
setting function enable

00 (disabling), 01 (enabling)

00

¯

{

4-79

b040

Torque limit selection

00 (quadrant-specific setting), 01 (switching by terminal), 02
(analog input), 03 (option 1), 04 (option 2)

00

¯

{

b041

Torque limit (1) (forward-driving
in 4-quadrant mode)

0. to 200. (%), no (disabling torque limitation)

150.

¯

{

b042

Torque limit (2)
(reverse-regenerating in
4-quadrant mode)

0. to 200. (%), no (disabling torque limitation)

150.

¯

{

b043

Torque limit (3) (reverse-driving
in 4-quadrant mode)

0. to 200. (%), no (disabling torque limitation)

150.

¯

{

b044

Torque limit (4)
(forward-regenerating in
4-quadrant mode)

0. to 200. (%), no (disabling torque limitation)

150.

¯

{

4-92

b045

Torque limit LADSTOP enable

00 (disabling), 01 (enabling)

00

¯

{

4-94

T

o

rque lim

it

at

ion

b046

Reverse Run protection enable

00 (disabling), 01 (enabling)

00

¯

{

4-93

b050

Controller deceleration and stop
on power loss

00 (disabling), 01 (nonstop deceleration to stop), 02 (DC voltage
constant control, with resume), 03 ( without resume)

00

¯

¯

b051

DC bus voltage trigger level
during power loss

0.0 to 999.9, 1000. (V)

0.0

¯

¯

b052

Over-voltage threshold during
power loss

0.0 to 999.9, 1000. (V)

0.0

¯

¯

b053

Deceleration time setting during
power loss

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

1.00

¯

¯

b054

Initial output frequency decrease
during power loss

0.00 to 10.00 (Hz)

0.00

¯

¯

b055

Proportional gain setting for
nonstop operation at power loss

0.00 to 2.55

0.20

{

{

Non-

st

op

oper

a

tion at

m

om

en

tar

y

power

fa

ilur

e

b056

Integral time setting for nonstop
operation at power loss

0.000 to 9.999 /10.00 to 65.53 (s)

0.100

{

{

4-83

b060

Maximum-limit level of window
comparators O

0. to 100. (lower limit : b061 + b062 / 2) (%)

100

{

{

b061

Minimum-limit level of window
comparators O

0. to 100. (lower limit : b060 - b062 / 2) (%)

0

{

{

b062

Hysteresis width of window
comparators O

0. to 10. (lower limit : b061 - b062 / 2) (%)

0

{

{

b063

Maximum-limit level of window
comparators OI

0. to 100. (lower limit : b064 + b066 / 2) (%)

100

{

{

b064

Minimum-limit level of window
comparators OI

0. to 100. (lower limit : b063 - b066 / 2) (%)

0

{

{

b065

Hysteresis width of window
comparators OI

0. to 10. (lower limit : b063 - b064 / 2) (%)

0

{

{

b066

Maximum-limit level of window
comparators OI

-100. to 100. (lower limit : b067 + b068 / 2) (%)

100

{

{

b067

Minimum-limit level of window
comparators O/OI/O2

-100. to 100. (lower limit : b066 - b068 / 2) (%)

0

{

{

b068

Hysteresis width of window
comparators O/OI/O2

0. to 10. (lower limit : b066 - b067 / 2) (%)

0

{

{

b070

Operation level at O
disconnection

0. to 100. (%) or "no" (ignore)

no

¯

{

b071

Operation level at OI
disconnection

0. to 100. (%) or "no" (ignore)

no

¯

{

Window com

p

ar

a

tor

b072

Operation level at O2
disconnection

-100. to 100. (%) or "no" (ignore)

no

¯

{

4-71

Advertising