Chapter 4 Explanation of Functions

4 -

74

4.2.82 AM and AMI terminals

The AM terminal outputs an analog voltage signal (0 to 10 V).

C028: [AM] siginal selection
C029: [AMI] siginal selection
C106: AM gain adjustment
C109: AM offset adjustment
C108: AMI gain adjustment
C110: AMI offset adjustment

Related code

You can monitor the inverter output frequency and output current via the AM
and AMI terminals on the control circuit block.

The AMI terminal outputs an analog current signal (4 to 20 mA).

(1) AM siginal selection /AMI signal selection
Select the signals to be output from the AM and AMI terminals among those shown below.

Item

Function code

Data

Description

Full-scale value

00

Output frequency

0 to maximum frequency (Hz) (*3)

01

Output current

0 to 200%

02

Output torque (*1)

0 to 200%

04 Output

voltage

0 to 133% (75% of full scale is
equivalent to 100%)

05

Input power

0 to 200%

06

Electronic thermal
overload

0 to 100%

07

LAD frequency

0 to maximum frequency (Hz)

09 Motor

temperature

0ºC to 200ºC (0ºC is output when the
motor temperature is 0ºC or less.)

10

Heat sink temperature

0ºC to 200ºC (0ºC is output when the
motor temperature is 0ºC or less.)

11

Output torque (signed)

(Output only from the AM terminal) 0
to 200% (*1) (*2)

13

General analog YA (1) (*4)

(Output only from the AM terminal) 0
to 100%

[AM] siginal
selection /
[AMI] siginal
selection

C028/C029

14

General analog YA (2) (*4)

(Output only from the AMI terminal) 0
to 100%

*1 This signal is output only when the V/F characteristic curve selection (see Section 4.2.18) is the

sensorless vector control, 0Hz-range sensorless vector control, or vector control with sensor.

*2 The specifications of the output torque (signed) are as follows:

200

100

10

5

0

AM output (V)

When the AM gain (C106) is 100%

When the AM gain (C106) is 200%

When the AM offset (C109) is 50%

Torque (%)












*3 The actually detected output frequency is output when the V/F characteristic curve selection is the

vector control with sensor (A044 = 05).

*4 For detail of the function, refer “Programing software EZ-SQ user manuaru”.

(2) AM/AMI adjustment
Adjust the inverter output gain for the external meters connected to the AM and AMI terminals.

Item

Function code

Range of data

Description

Setting of the gain for AM monitoring

C106

50. to 200. (%)

Setting of the gain for AM monitoring

Setting of the offset for AM monitoring

C109

0 to 100 (%)

Setting of the offset for AM monitoring

Setting of the gain for AMI monitoring

C107

50. to 200. (%)

Setting of the gain for AMI monitoring

Setting of the offset for AMI monitoring

C110

0 to 100 (%)

Setting of the offset for AMI monitoring

Note: The offset data is in percentage (%).

(Example) When the current range of AMI terminal output is 4 to 20 mA (default), the offset of 4 mA
is 20%.