Chapter 4 explanation of functions – Hitachi SJ700-2 User Manual

Page 111

Advertising
background image

Chapter 4 Explanation of Functions

(1) Binary operation mode
Assign functions "02" (CF1) to "05" (CF4) individually to the terminal [1] to [8] functions (C001 to C008) to
make multispeed s 0 to 15 available for selection.
Specify the desired frequencies for speeds 1 to 15 by setting multispeeds 1 to 15 (A021 to A035).
You can set speed 0 by using function "A020", "A220", "A320", or "F001" (see Section 4.2.1) when you
have specified the digital operator for the frequency source setting. You can set speed 0 by using the O, OI,
or O2 terminal when you have specified the control circuit board for the frequency source setting.

CF4

FW

CF3

CF2

CF1

Speed 1

Speed 2

Speed 3

Speed 4

Speed 5

Speed 6

Speed 7

Speed 8

Speed 9

Speed 10

Speed 11

Speed 12

Speed 13

Speed 14

Speed 15

Speed 0

Frequency input from
the digital operator or
via an external analog
input terminal

Multispeed CF4 CF3 CF2 CF1

Speed

0 OFF OFF OFF OFF

Speed 1

OFF

OFF

OFF

ON

Speed

2 OFF OFF ON OFF

Speed 3

OFF

OFF

ON

ON

Speed 4

OFF

ON

OFF

OFF

Speed

5 OFF ON OFF ON

Speed 6

OFF

ON

ON

OFF

Speed 7

OFF

ON

ON

ON

Speed 8

ON

OFF

OFF

OFF

Speed 9

ON

OFF

OFF

ON

Speed

10 ON OFF ON OFF

Speed

11 ON OFF ON ON

Speed 12

ON

ON

OFF

OFF

Speed 13

ON

ON

OFF

ON

Speed 14

ON

ON

ON

OFF

Speed

15 ON ON ON ON

- With multispeed binary operation mode, you can use the multistage speed/position determination time
setting (C169) to specify a delay to be set until the relevant terminal input is determined. Use this
specification to prevent the application of fluctuating terminal input before it is determined.
- The input data is finally determined when terminal input becomes stable after the delay set as C169.
(Note that a long determination time deteriorates the input terminal response.)

Determination time

CF1

CF2

CF3

Frequency

13

1

5

9

Determination time (C169) = 0

11

CF4

15

Determination time (C169) specified

4










(2) Bit operation mode
- Assign functions "32" (SF1) to "38" (SF7) individually to the terminal [1] to [8] functions (C001 to C008) to
make multispeed s 0 to 7 available for selection.

- Specify the desired frequencies for speeds 1 to 7 (SF1 to SF7)

SF1

SF2

SF3

SF4

SF5

FW

SF6

SF7

Frequency input from
the digital operator or
via an external analog
input terminal

Speed 1

Speed 2

Speed 3

Speed 4

Speed 5

Speed 6

Speed 7

Speed 0

Speed 1

by setting multispeeds 1 to 7 (A021 to A027).

Multispeed

SF7 SF6 SF5 SF4 SF3 SF2 SF1

Speed

0 OFF OFF OFF OFF OFF OFF OFF

Speed 1

Ч

Ч

Ч

Ч

Ч

Ч ON

Speed 2

Ч

Ч

Ч

Ч

Ч ON OFF

Speed 3

Ч

Ч

Ч

Ч ON OFF

OFF

Speed 4

Ч

Ч

Ч ON OFF

OFF

OFF

Speed 5

Ч

Ч ON OFF OFF OFF OFF

Speed 6

× ON OFF OFF OFF OFF OFF

Speed

7 ON OFF OFF OFF OFF OFF OFF

If two or more input terminals are turned on at the same
time, the terminal given the smallest terminal number
among them has priority over others. The "X" mark in the above table indicates that the speed can be
selected, regardless of whether or not the corresponding terminal is turned on.

4 -

48

Advertising