Chapter 4 explanation of functions, 4 - 148 (v) list of registers (function modes) – Hitachi SJ700-2 User Manual

Page 211

Advertising
background image

Chapter 4 Explanation of Functions

4 - 148

(v) List of registers (function modes)

Register

No.

Function name

Function code

R/W

Monitoring and setting items

Data

resolution

1201h

Frequency source setting

A001

R/W

0 (keypad potentiometer), 1 (control circuit terminal
block), 2 (digital operator), 3 (RS485), 4 (option 1), 5
(option 2), 6 (pulse train input), 7 (easy sequence),
10 (operation function result)

-

1202h

Run command source
setting

A002 R/W

1 (control circuit terminal block), 2 (digital operator),
3 (RS485), 4 (option 1), 5 (option 2)

-

1203h

Base frequency setting

A003

R/W 30 to "maximum frequency"

1 [Hz]

1204h

Maximum frequency setting

A004

R/W 30 to 400

1 [Hz]

1205h [AT]

selection

A005

R/W

0 (switching between O and OI terminals), 1
(switching between O and O2 terminals), 2
(switching between O terminal and keypad
potentiometer), 3 (switching between OI terminal and
keypad potentiometer), 4 (switching between O2 and
keypad potentiometer)

-

1206h [O2]

selection

A006

R/W

0 (single), 1 (auxiliary frequency input via O and OI
terminals) (nonreversible), 2 (auxiliary frequency
input via O and OI terminals) (reversible), 3
(disabling O2 terminal)

-

1207h to

120Ah

(Reserved) -

-

Inaccessible

-

120Bh A011

(high)

120Ch

[O]-[L] input active range
start frequency

A011 (low)

R/W 0 to 40000

0.01 [Hz]

120Dh A012

(high)

120Eh

[O]-[L] input active range end
frequency

A012 (low)

R/W 0 to 40000

0.01 [Hz]

120Fh

[O]-[L] input active range
start voltage

A013

R/W 0 to "[O]-[L] input active range end voltage"

1 [%]

1210h

[O]-[L] input active range end
voltage

A014

R/W "[O]-[L] input active range start voltage" to 100

1 [%]

1211h

[O]-[L] input active range
start frequency selection

A015

R/W 0 (external start frequency), 1 (0 Hz)

-

1212h

External frequency filter time
const.

A016

R/W 1 to 30 or 31 (500 ms filter ±0.1 Hz with hysteresis)

1

1213h

Easy sequence function
selection

A017

R/W 0 (disabling), 1 (enabling)

-

1214h (Reserved)

-

R/W

Inaccessible

-

1215h

Multispeed operation
selection

A019

R/W 0 (binary), 1 (bit)

-

1216h A020

(high)

R/W

1217h

Multispeed frequency setting

A020 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

1218h A021

(high)

R/W

1219h

Multispeed 1 setting

A021 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

121Ah A022

(high)

R/W

121Bh

Multispeed 2 setting

A022 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

121Ch A023

(high)

R/W

121Dh

Multispeed 3 setting

A023 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

121Eh A024

(high)

R/W

121Fh

Multispeed 4 setting

A024 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

1220h A025

(high)

R/W

1221h

Multispeed 5 setting

A025 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

1222h A026

(high)

R/W

1223h

Multispeed 6 setting

A026 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

1224h A027

(high)

R/W

1225h

Multispeed 7 setting

A027 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

1226h A028

(high)

R/W

1227h

Multispeed 8 setting

A028 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

1228h A029

(high)

R/W

1229h

Multispeed 9 setting

A029 (low)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

122Ah

Multispeed 10 setting

A030 (high)

R/W 0 or "start frequency" to "maximum frequency"

0.01 [Hz]

122Bh A030

(low)

R/W

122Ch


Multispeed 11 setting

A031 (high)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

122Dh A031

(low)

R/W

122Eh


Multispeed 12 setting

A032 (high)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

122Fh A032

(low)

R/W

1230h


Multispeed 13 setting

A033 (high)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

1231h A033

(low)

R/W

1232h


Multispeed 14 setting

A034 (high)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]

1233h A034

(low)

R/W

1234h


Multispeed 15 setting

A035 (high)

R/W

0 or "start frequency" to "maximum frequency"

0.01 [Hz]