Chapter 6 Maintenance and Inspection

6.8 Methods of Measuring the Input/Output Voltages, Current, and Power

This section describes the measuring instruments generally used to measure the input and output voltages,
output current, and output power of the inverter.

I

R

I

S

I

T

E

R

E

T

E

S

W

I2

W

I3

W

I1

R

T

S

U

V

W

I

U

I

V

I

W

E

U

E

W

E

V

W

O2

W

O1

W

V

U

R

S

T

Power supply

Invert

er

Motor

Measurement

item

Measuring point

Measuring instrument

Remarks

Reference values

Input voltage (E

IN

) Across R-S, S-T, and T-R

(E

R

), (E

S

), and (E

T

)

Moving-iron voltmeter
or
rectifier-type voltmeter

Effective value of
full waves

200 V class models:
200 to 240 V, 50/60 Hz
400 V class
380 to 480 V, 50/60 Hz

Input current (I

IN

)

Current at R, S, and T
(I

R

), (I

S

), and (I

T

)

Moving-iron ammeter

Effective value of
full waves

When input currents are
unbalanced
I

IN

= (I

R

+ I

S

+ I

T

)/3

Input power (W

IN

) Across R-S, S-T, and T-R

(W

11

) + (W

12

) + (W

13

)

Electrodynamometer-type
wattmeter

Effective value of
full waves

3-wattmeter method

input power factor
(Pf

IN

)

Calculated from the measured input voltage (E

IN

), input current (I

IN

), and input power

(W

IN

)


Output voltage
(E

OUT

)

Across U-V, V-W, and W-U
(E

U

), (E

V

), and (EW)

Method shown in the figure
below
or
rectifier-type voltmeter

Effective value of
fundamental wave

Output current
(I

OUT

)

Current at U, V, and W
(I

U

), (IV), and (IW)

Moving-iron ammeter

Effective value of
full waves

Output power
(W

OUT

)

Across U-V and V-W
(W

01

) + (W

02

)

Electrodynamometer-type
wattmeter

Effective value of
full waves

2-wattmeter method
(or 3-wattmeter method)

6 - 6

W

IN

×100(%)

√3・E

IN

・I

IN

Pf

IN

Output power
factor (Pf

OUT

)

Calculated from the measured input
voltage (E

OUT

), input current (I

OUT

),

and input power (W

OUT

)

Pf

OUT

W

OUT

√3・E

OUT

・I

OUT

×100(%)


Notes:
1. To measure the output voltage, use

an instrument that reads the
effective value of the fundamental
wave. To measure the current or
power, use an instrument that reads
the effective value of full waves.

2. Since the inverter output waveform

is controlled by PWM, it has a large
margin of error, especially at low
frequencies. In many cases, general
testers may be inapplicable for the
measurement because of the
adverse effect of noise.

Diode

600 V, 0.1 A or more
(200 V class model)
1,000 V, 0.1 A or more
(400 V class model)

Effective value of
fundamental wave (V

AC

)

V

AC

= 1.1 x V

DC

R

T

S

Inv

e

rter

U

V

W

Motor

2W 220k

Moving-coil voltmeter
300 V (200 V class
model)
600 V (400 V class
model)

V

DC

+

Method to measure the output voltage

Advertising