Chapter 4 Explanation of Functions

(vii) Writing data to multiple registers [10h]
This function writes data to sequential registers.

(Example)
When setting "3,000 Hz" as the Acceleration (1) time (F002) in the inverter at slave address "1":
Since register "1103h" and "1104h" to store the Acceleration (1) time (F002) have a data resolution of
0.01 seconds, specify "300000" (493E0h) as the updating data to set "3,000 seconds".






















If the function to write data to multiple registers cannot be executed normally, the inverter will return an
exception response. For details, see Item (viii), "Exception response."

(viii) Exception response
The master system requests the inverter (slave) to return a response upon reception of a query other
than broadcasted queries. The inverter must return the response that matches the query it has received.
However, if an error is found in a query, the inverter will return an exception response.

The exception response consists of the following fields:

Field configuration

Slave address
Function code

Exception code

CRC-16 code

Details of the field configuration are described below. The exception response in reply to a query includes
a function code that is the sum of "80h" and the function code specified by the query. The exception code
in the exception response indicates the content of the error.

4 - 140


Query

Field name

Sample setting
(hexadecimal)

1

Slave address (*1)

01

2 Function

code

10

3

Starting register address
(upper digit) (*2)

11

4

Starting register address
(lower digit) (*2)

02

5

Number of registers (upper
digit)

00

6

Number of registers (lower
digit)

02

7

Number of data bytes (*3)

04

8

Updating data 1 (upper digit)

00

9

Updating data 1 (lower digit)

04

10 Updating data 2(upper digit)

93

11

Updating data 2(lower digit)

E0

12

CRC-16 code (upper digit)

9E

13

CRC-16 code (lower digit)

9F

*1 If this query is broadcasted, no inverter will return any response.
*2 Note that the starting register address is 1 less than the actual

address of the register to which the data is to be written first.

*3 As the number of bytes, do not specify the number of registers but

the number of bytes to be actually updated.

Response

Field name

Sample setting
(hexadecimal)

1

Slave address (*1)

01

2 Function

code

10

3

Starting register address (upper
digit) (*2)

11

4

Starting register address (lower
digit) (*2)

02

5

Number of registers (upper
digit)

00

6

Number of registers (lower digit)

02

7

CRC-16 code (upper digit)

E5

8

CRC-16 code (lower digit)

34

unction codes

Query Exception

response

F

01h 81h

03h 83h

05h 85h

06h 86h

0Fh 8Fh

10h 90h

Exception codes

Code Description

01h

An unsupported function is specified.

02h

The specified address is not found.

03h

The specified data has an unacceptable format.

21h

The data to be written to a register exceeds the range of inverter
specifications.

22h

The inverter restricts the execution of the specified function:
- Rewriting a register that cannot be rewritten during the operation
- Issuing an Enter command during the operation (in undervoltage

status)

- Writing to a register during tripping (because of undervoltage)
- Writing to a read-only register (coil)