Chapter 2 Installation and Wiring

(2) Layout of main circuit terminals

The figures below show the terminal layout on the main circuit terminal block of the inverter.

Terminal layout

Inverter model

SJ700-055 to

SJ700-075LFF2

SJ700-055 to

SJ700-075HFF2

R0 and T0: M4

Ground terminal: M6

Other terminals: M6

RB

R

(L1)

S

(L2)

T

(L3)

PD

(+1)

P

(+)

N

(-)

U

(T1)

V

(T2)

W

(T3)

R0 T0

G

G

SJ700-110LFF

SJ700-110HFF

R0 and T0: M4

Ground terminal: M6

Other terminals: M6

SJ700-150 to

SJ700-185LFF

SJ700-150 to

SJ700-220HFF

R0 and T0: M4

Ground terminal: M6

Other terminals: M6

Jumper connecting
terminals PD and P

When not using the DCL,
do not remove the jumper
from terminals PD and P.

Ground terminal with
jumper (shaded in the
figure) to enable/disable the
EMC filter function

[Method of enabling/disabling the EMC filter function]

Disabling the EMC filter (factory setting)

Enabling the EMC filter

RB

R

(L1)

S

(L2)

T

(L3)

PD

(+1)

P

(+)

N

(-)

U

(T1)

V

(T2)

W

(T3)

R0 T0

G

G

SJ700-220LFF

R0 and T0: M4

Ground terminal: M6

Other terminals: M8

Charge lamp

Jumper connecting
terminals PD and P

2 - 16

Ground terminal with
jumper (shaded in the
figure) to enable/disable the
EMC filter function

When not using the DCL,
do not remove the jumper
from terminals PD and P.

[Method of enabling/disabling the EMC filter function]

Disabling the EMC filter (factory setting)

Enabling the EMC filter