Chapter 4 Explanation of Functions

4.2.33 Start frequency setting

b082: Start frequency adjustment

Related code

The start frequency setting function allows you to specify the inverter
output frequency that the inverter initially outputs when an operation
command is input.
Use this function mainly to adjust the start torque.
If the start frequency (b082) is set too high, the inverter will start the motor with a full voltage, which will
increase the start current. Such status may trigger the overload restriction operation or make the inverter
prone to easily tripping because of the overcurrent protection.
Specifying "04" (0SLV: 0Hz-range sensorless vector control) or "05" (V2: vector control with sensor) for the
V/F characteristic curve selection (A044) disables the start frequency setting function.

Item

Function code

Range of data

Description

Start frequency
adjustment

b082

0.10 to 9.99 (Hz)

Setting of the start frequency



FW

requency

age

b082

Output f

Output volt











4.2.34 Reduced voltage start function

b036: Reduced voltage start selection
b082: Start frequency adjustment

Related code

The reduced voltage start function enables you to make the inverter
increase the output voltage gradually when starting the motor.
Set a small value for the reduced voltage start selection (b036) if you
intend to increase the start torque. On the other hand, setting a small
value will cause the inverter to perform full-voltage starting and to easily
trip because of overcurrent.

Item

Function code

Range of data

Description

00

Disabling the reduced voltage starting

Reduced voltage start
selection

b036

01 to 255

01: Short (about 6 ms)

255: Long (about 1.53 s)


00

01 06

・・・

Reduced Voltage Start

b036

Start frequency
b082

FW

Output frequency

Output voltage










4 - 4