Chapter 4 Explanation of Functions

4 - 144

(ii) List of registers (frequency settings and trip monitoring)

Register

No.

Function name

Function

code

R/W

Monitoring and setting items

Data

resolution

0001h F001

(high)

R/W

0002h

Frequency source setting

F001 (low)

R/W

0 to 40000 (valid when A001 = 03)

0.01 [Hz]

0003h Inverter

status

A

-

R

0: Initial status, 1: Waiting for Vdc establishment,
2: Stopping, 3: Running, 4: Free-run stop (FRS),
5: Jogging, 6: DC braking, 7: Frequency being
input, 8: Retrying operation, 9: Undervoltage
(UV),

-

0004h Inverter status B

-

R

0: Stopping, 1: Running, 2: Tripping

-

0005h Inverter status C

-

R

0: ---, 1: Stopping, 2: Decelerating, 3: Constant-
speed operation, 4: Accelerating, 5: Forward
rotation, 6: Reverse rotation, 7: Switching from
forward rotation to reverse rotation, 8: Switching
from reverse rotation to forward rotation, 9:
Starting forward rotation, 10: Starting reverse
rotation

-

0006h PID feedback

-

R/W 0 to 10000

0.01 [%]

0007h

to

0010h

(Reserved) -

R

Inaccessible

-

0011h Trip Counter

d080

R

0 to 65530

1 [time]

0012h Trip monitoring 1 (factor)

See the list of inverter trip factors below

-

0013h Trip monitoring 1 (inverter status)

See the list of inverter trip factors below

-

0014h Trip monitoring 1 (frequency) (high)
0015h Trip monitoring 1 (frequency (low)

0 to 40000

0.01 [Hz]

0016h Trip monitoring 1 (current)

Output current at tripping

0.1 A

0017h Trip monitoring 1 (voltage)

DC input voltage at tripping

1 V

0018h Trip monitoring 1 (running time) (high)
0019h Trip monitoring 1 (running time) (low)

Cumulative running time at tripping

1h

001Ah Trip monitoring 1 (power-on time) (high)
001Bh Trip monitoring 1 (power-on time) (low)

d081 R

Cumulative power-on time at tripping

1h

001Ch Trip monitoring 2 (factor)

See the list of inverter trip factors below

-

001Dh Trip monitoring 2 (inverter status)

See the list of inverter trip factors below

-

001Eh Trip monitoring 2 (frequency) (high)
001Fh Trip monitoring 2 (frequency (low)

0 to 40000

0.01 [Hz]

0020h Trip monitoring 2 (current)

Output current at tripping

0.1 A

0021h Trip monitoring 2 (voltage)

DC input voltage at tripping

1 V

0022h Trip monitoring 2 (running time) (high)
0023h Trip monitoring 2 (running time) (low)

Cumulative running time at tripping

1h

0024h Trip monitoring 2 (power-on time) (high)
0025h Trip monitoring 2 (power-on time) (low)

d082 R

Cumulative power-on time at tripping

1h

0026h Trip monitoring 3 (factor)

See the list of inverter trip factors below

-

0027h Trip monitoring 3 (inverter status)

See the list of inverter trip factors below

-

0028h Trip monitoring 3 (frequency) (high)
0029h Trip monitoring 3 (frequency (low)

0 to 40000

0.01 [Hz]

002Ah Trip monitoring 3 (current)

Output current at tripping

0.1 A

002Bh Trip monitoring 3 (voltage)

DC input voltage at tripping

1 V

002Ch Trip monitoring 3 (running time) (high)
002Dh Trip monitoring 3 (running time) (low)

Cumulative running time at tripping

1h

002Eh Trip monitoring 3 (power-on time) (high)
002Fh Trip monitoring 3 (power-on time) (low)

d083 R

Cumulative power-on time at tripping

1h

0030h Trip monitoring 4 (factor)

See the list of inverter trip factors below

-

0031h Trip monitoring 4 (inverter status)

See the list of inverter trip factors below

-

0032h Trip monitoring 4 (frequency) (high)
0033h Trip monitoring 4 (frequency (low)

0 to 40000

0.01 [Hz]

0034h Trip monitoring 4 (current)

Output current at tripping

0.1 A

0035h Trip monitoring 4 (voltage)

DC input voltage at tripping

1 V

0036h Trip monitoring 4 (running time) (high)
0037h Trip monitoring 4 (running time) (low)

Cumulative running time at tripping

1h

0038h Trip monitoring 4 (power-on time) (high)
0039h Trip monitoring 4 (power-on time) (low)

d084 R

Cumulative power-on time at tripping

1h