Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

101

The actual active drive data set (DDS) is displayed in parameter r0051[1].

r0055

Bit05

r0055

Bit04

1. DDS

0

0

2. DDS

0

1

3. DDS

1

0

3. DDS

1

1

r0051 [0]

0
1

2

2

r0051 [1]

0
1

2

2

selected

DDS

active

DDS

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)

Example:

a) Commissioning procedure with one motor:
-

Apply commissioning to DDS1

-

Connect P0820 (P0821 if necessary) with DDS source (i.e. via DIN 4: P0704[0] = 99, P0820 = 722.3)

-

Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2)

-

Adapt DDS2 parameters (e.g. Ramp-up time P1120[1] and Ramp-down time P1121[1])

DIN

ADC

P0820 = 722.3

SUM

Setpoint

Sequence control

DIN4

AFM

RFG

Motor

control

0

1

P1120
P1121

[0]

DDS1

[1]

DDS2

[2]

DDS3

M

M

odul

at

or


b) Commissioning procedure with two motors (Motor 1, Motor 2):
-

Commission Motor 1; Adapt all other DDS1 parameters (as required)

-

Connect P0820 (P0821 if necessary) with DDS source (i.e. via DIN 4: P0704[0] = 99, P0820 = 722.3)

-

Switch-over to DDS2 (check it via r0051)

-

Commission Motor 2; Adapt all other DDS2 parameters (as required)

MM4

M1

K1

M2

K2

Motor 1

Motor 2

Note:

P0821 is also relevant for drive data set (DDS) selection.