Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

210

6SE6400-5BB00-0BP0

Example:

P2115[0] = 13625
P2115[1] = 2579
P2115[2] = 516

The conversion into binary quantities (U16) results in the following bit pattern:
Seconds + minutes:
-

High byte (MSB) = 00110101 corresponding to the number 53, i.e. seconds 53

-

Low byte (LSB) = 00111001 corresponding to the number 57, i.e. minutes 57


Hours + days:
-

High byte (MSB) = 00001010 corresponding to the number 10, i.e. hours 10

-

Low byte (LSB) = 00010011 corresponding to the number 19, i.e. days 19


Months + year:
-

High byte (MSB) = 00000010 corresponding to the number 2, i.e. months 2

-

Low byte (LSB) = 00000100 corresponding to the number 4, i.e. years 4


This means that the real time displayed in P2115 is 19.02.2004, 10:57:53.

P2120 Indication

counter

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 65535

Indicates total number of alarm events. This parameter is incremented whenever an alarm event occurs. It
also gets incremented when a warning is cleared or faults are cleared.

This parameter is used by the PC tools.

P2150[3]

Hysteresis frequency f_hys

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

3.00

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10.00

Defines hysteresis level applied for comparing frequency and speed to threshold as illustrated in the
diagram below.

-1

1

0

0

1

{

-

0

1

{

0

Hyst. freq. f_hys

0.00 ... 10.00 [Hz]

P2150.D (3.00)

Hyst . freq. f_hys

0.00 ... 10.00 [Hz]

P2150.D (3.00)

f_act > 0

| f_act | >= | f_set |

f_act > 0

| f_act| >= | f_set |

f_act

f_set

r2197 Bit03
r0052 Bit14

r2197 Bit04
r0053 Bit06

Index:

P2150[0] : 1st. Drive data set (DDS)
P2150[1] : 2nd. Drive data set (DDS)
P2150[2] : 3rd. Drive data set (DDS)

P2153[3]

Time-constant frequency filter

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

5

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 1000

Specifies time constant of first-order frequency filter. The filtered frequency is then compared to the
thresholds.

Index:

P2153[0] : 1st. Drive data set (DDS)
P2153[1] : 2nd. Drive data set (DDS)
P2153[2] : 3rd. Drive data set (DDS)

Details:

See diagram in P2155, P2157 and P2159

Level

4

Level

3

Level

2