Issue 01/06 parameter description – Siemens 440 User Manual

Page 85

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

85

P0732[3]

BI: Function of digital output 2

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

52:7

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of digital output 2.

Index:

P0732[0] : 1st. Command data set (CDS)
P0732[1] : 2nd. Command data set (CDS)
P0732[2] : 3rd. Command data set (CDS)

Common Settings:

52.0

Drive ready

0 Closed

52.1

Drive ready to run

0 Closed

52.2

Drive running

0 Closed

52.3

Drive fault active

0 Closed

52.4

OFF2 active

1 Closed

52.5

OFF3 active

1 Closed

52.6

Switch on inhibit active

0 Closed

52.7

Drive warning active

0 Closed

52.8

Deviation setpoint/actual value

1 Closed

52.9

PZD control (Process Data Control)

0 Closed

52.A

Maximum frequency reached

0 Closed

52.B

Warning: Motor current limit

1 Closed

52.C

Motor holding brake (MHB) active

0 Closed

52.D

Motor overload

1 Closed

52.E

Motor running direction right

0 Closed

52.F

Inverter overload

1 Closed

53.0

DC brake active

0 Closed

53.1

Act. freq. f_act > P2167 (f_off)

0 Closed

53.2

Act. freq. f_act <= P1080 (f_min)

0 Closed

53.3

Act. current r0027 > P2170

0 Closed

53.4

Act. freq. f_act > P2155 (f_1)

0 Closed

53.5

Act. freq. f_act <= P2155 (f_1)

0 Closed

53.6

Act. freq. f_act >= setpoint

0 Closed

53.7

Act. Vdc r0026 < P2172

0 Closed

53.8

Act. Vdc r0026 > P2172

0 Closed

53.A

PID output r2294 == P2292 (PID_min) 0 Closed

53.B

PID output r2294 == P2291 (PID_max) 0 Closed

P0733[3]

BI: Function of digital output 3

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of digital output 3.

Index:

P0733[0] : 1st. Command data set (CDS)
P0733[1] : 2nd. Command data set (CDS)
P0733[2] : 3rd. Command data set (CDS)

Common Settings:

52.0

Drive ready

0 Closed

52.1

Drive ready to run

0 Closed

52.2

Drive running

0 Closed

52.3

Drive fault active

0 Closed

52.4

OFF2 active

1 Closed

52.5

OFF3 active

1 Closed

52.6

Switch on inhibit active

0 Closed

52.7

Drive warning active

0 Closed

52.8

Deviation setpoint/actual value

1 Closed

52.9

PZD control (Process Data Control)

0 Closed

52.A

Maximum frequency reached

0 Closed

52.B

Warning: Motor current limit

1 Closed

52.C

Motor holding brake (MHB) active

0 Closed

52.D

Motor overload

1 Closed

52.E

Motor running direction right

0 Closed

52.F

Inverter overload

1 Closed

53.0

DC brake active

0 Closed

53.1

Act. freq. f_act > P2167 (f_off)

0 Closed

53.2

Act. freq. f_act <= P1080 (f_min)

0 Closed

53.3

Act. current r0027 > P2170

0 Closed

53.4

Act. freq. f_act > P2155 (f_1)

0 Closed

53.5

Act. freq. f_act <= P2155 (f_1)

0 Closed

53.6

Act. freq. f_act >= setpoint

0 Closed

53.7

Act. Vdc r0026 < P2172

0 Closed

53.8

Act. Vdc r0026 > P2172

0 Closed

53.A

PID output r2294 == P2292 (PID_min) 0 Closed

53.B

PID output r2294 == P2291 (PID_max) 0 Closed

Level

2

Level

2

Advertising