6SE6400-5BB00-0BP0

P1094[3]

Skip frequency 4

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

0.00

P-Group: SETPOINT

Active: Immediately

QuickComm.: No

Max: 650.00

Defines skip frequency 4 which avoids effects of mechanical resonance and suppresses frequencies within
+/- P1101 (skip frequency bandwidth).

Index:

P1094[0] : 1st. Drive data set (DDS)
P1094[1] : 2nd. Drive data set (DDS)
P1094[2] : 3rd. Drive data set (DDS)

Details:

See P1091 (skip frequency 1).

P1101[3]

Skip frequency bandwidth

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

2.00

P-Group: SETPOINT

Active: Immediately

QuickComm.: No

Max: 10.00

Delivers frequency bandwidth to be applied to skip frequencies (in [Hz]).

Index:

P1101[0] : 1st. Drive data set (DDS)
P1101[1] : 2nd. Drive data set (DDS)
P1101[2] : 3rd. Drive data set (DDS)

Details:

See P1091 (skip frequency 1).

P1110[3]

BI: Inhibit neg. freq. setpoint

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

This parameter suppresses negative setpoints. Therefore, modification of the motor direction is inhibited to
the setpoint channel.

Index:

P1110[0] : 1st. Command data set (CDS)
P1110[1] : 2nd. Command data set (CDS)
P1110[2] : 3rd. Command data set (CDS)

Common Settings:

0 = Disabled
1 = Enabled

Notice:

Where
-

If a min. frequency (P1080) and a negative setpoint are given, the motor is accelerated by a positive
value in relationship to the min. frequency.

-

This function does not disable the "reverse command functions" (e.g. Reverse, ON left); rather, a
reverse command causes motor to run in the positive direction only, as described above.

f

t

0

1

t

f (r1170)

set

ON/OFF1

0

1

t

Reverse

f (r1078)

set

P1110 = 1

P1080

-P1080

Level

3

Level

3

Level

3