A0920 ADC parameters not correctly set

Cause

ADC parameters should not be set to identical values, as this would lead to illogical results.
-

Index 0: Parameter settings for output identical.

-

Index 1: Parameter settings for input identical.

-

Index 2: Parameter settings for input do not correspond to ADC type.

A0921 DAC parameters not set properly

Cause

-

DAC parameters (P0777 and P0779) have identical values.

OR
-

DAC parameters (P0778 and P0780) have identical values.

Identical values would produce illogical results.

Diagnosis & Remedy

Check the following:
-

Output parameter settings. Ensure P0777 and P0779 are not identical.

-

Input parameter settings. Ensure P0778 and P0780 are not identical.

A0922 No load at the inverter

Cause

-

no load is connected to the inverter.

-

therefore several functions can run differently than under normal load conditions.

A0923 JOG counter-clockwise as well as JOG clockwise are requested

Cause

-

both JOG clockwise and JOG counter-clockwise (P1055/P1056) have been requested. This is the
reason that the RFG output frequency has been frozen to the actual value.

A0952 Load fault detected

Cause

-

load conditions at the motor indicate a load fault or mechanical fault.

Diagnosis & Remedy

Please check the following:
-

no braking, failure or destruction of the mechanical transmission line

-

if required, lubricate the mechanical transmission line.

If you are using an external encoder, please check the following parameter settings:
-

P2192 (delay time, load torque monitoring)

If you are using a specific speed range, then please check the following:
-

P2182 (load torque monitoring F1)

-

P2183 (load torque monitoring F1f2)

-

P2184 (load torque monitoring F1f3)

-

P2185 (upper torque threshold 1)

-

P2186 (lower torque threshold 1)

-

P2187 (upper torque threshold 2)

-

P2188 (lower torque threshold 2)

-

P2189 (upper torque threshold 3)

-

P2190 (lower torque threshold 3)

-

P2192 (delay time, load torque monitoring)

A0936 PID auto tuning active

Cause

-

PID auto tuning (P2350) is selected or is presently running.

Diagnosis & Remedy

-

after automatic PID optimization has been completed, the alarm is reset.