Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

51

P0304[3] Rated

motor

voltage

Min: 10

CStat:

C

Datatype: U16 Unit:

V

Def:

230

P-Group: MOTOR

Active: first confirm

QuickComm.: Yes Max: 2000

Nominal motor voltage [V] from rating plate. Following diagram shows a typical rating plate with the
locations of the relevant motor data.

X

1 AC 110 V *)

-
-
-
-

1 AC 230 V

X

-

X

-

X

3 AC 230 V

-
-

X

-

X

3 AC 400 V

-

X
X
X
X

3 AC 500 V

-
-
-
-

X

MICROMASTER 410
MICROMASTER 411
MICROMASTER 420
MICROMASTER 430
MICROMASTER 440

*) Line supply voltage 1-ph. 110 V AC is stepped-up --> frequency inverter output voltage 3-ph. 230 V AC

Line supply voltage

Index:

P0304[0] : 1st. Drive data set (DDS)
P0304[1] : 2nd. Drive data set (DDS)
P0304[2] : 3rd. Drive data set (DDS)

Dependency:

-

Changeable only when P0010 = 1 (quick commissioning).

-

Default value is depending on inverter type and its rating data.

Caution:

The input of rating plate data must correspond with the wiring of the motor (star / delta). This means, if delta
wiring is used for the motor, delta rating plate data has to be entered.

W2

U1

U2

V1

V2

W1

W2

U1

U2

V1

V2

W1

Delta connection

U1

V1
W1

U1

V1
W1

Star connection

IEC Motor

e.g.: Volts 230 V (Delta connection) / 400 V (Star connection)

Level