Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

98

6SE6400-5BB00-0BP0

P0809[3]

Copy command data set (CDS)

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 2

Calls "copy Command Data Set (CDS)" function.
The list of all Command Data Sets (CDS) are shown in the opening instructions of the Parameter List (PLI).

Index:

P0809[0] : Copy from CDS
P0809[1] : Copy to CDS
P0809[2] : Start copy

Example:

Copying of all values from CDS1 to CDS3 can be accomplished by the following procedure:

P0809[0] = 0
P0809[1] = 2

P0809[2] = 1

2. CDS 3. CDS

P0700
P0701
P0702
P0703
P0704

..

..

.

P2253
P2254
P2264

..

..

.

..

..

.

..

..

.

[0]

[1]

[2]

1. CDS

1. CDS

3. CDS
Start copy

Note:

Start value in index 2 is automatically reset to "0" after execution of function.

P0810

BI: CDS bit 0 (Local / Remote)

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4095:0

Selects command source from which to read Bit 0 for selecting a command data set (CDS).

t

0

1

2

3

(0:0)

BI: CDS b0 loc/rem

P0810

(0:0)

BI: CDS bit 1

P0811

t

0

1

2

3

CO/BO: Act CtrlWd2

r0055

r0055

CO/BO: Act

CtrlWd1

r0054

r0054

.15

.15

.15

.15

r0050

CDS active

Selecting

CDS

approx.
4 ms

approx.
4 ms

r0050

CO: Active CDS

Changeover

time

Changeover

time

Level

2

Level

2