Siemens 440 User Manual

Page 235

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

235

P2261

PID setpoint filter timeconstant

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

s

Def:

0.00

P-Group: TECH

Active: Immediately

QuickComm.: No

Max: 60.00

Sets a time constant for smoothing the PID setpoint.

Note:

0 = no smoothing

r2262

CO: Filtered PID setp. after RFG

Min: -

Datatype: Float Unit:

%

Def:

-

P-Group: TECH

Max: -

Displays the filtered PID setpoint after the PID ramp-function generator (PID_HLG) as percentage.
Parameter r2262 is obtained from the filtered parameter r2260 that is filtered using the PT1 filter with time
constant P2261.

Note:

r2262 = 100 % corresponds to 4000 hex

P2263

PID controller type

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: TECH

Active: Immediately

QuickComm.: No

Max: 1

Sets the PID controller type.

Possible Settings:

0

D component on feedback signal

1

D component on error signal

P2264[3]

CI: PID feedback

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

755:0

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 4000:0

Selects the source of the PID feedback signal.

Index:

P2264[0] : 1st. Command data set (CDS)
P2264[1] : 2nd. Command data set (CDS)
P2264[2] : 3rd. Command data set (CDS)

Common Settings:

Parameter

BI: Enable PID controller

P2200

Parameter text

Setting

Meaning

0

PID controller always active

1.0

CI: PID setpoint

P2253

Analog input 1

755.0

USS on BOP link

2015.1

USS on COM link

2019.1

CB on COM link

2050.1

CI: PID feedback

P2264

755.0

Analog input 1

Analog input 2

755.1

PID mode

P2251

0

PID as setpoint

2224

Fixed PID setpoint (PID-FF)
PID-MOP

2250

PID controller de-activated

BICO

Digital input x

722.x

BICO parameter

Note:

When analog input is selected, offset and gain can be implemented using parameters P0756 to P0760
(ADC scaling).

P2265

PID feedback filter timeconstant

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

s

Def:

0.00

P-Group: TECH

Active: Immediately

QuickComm.: No

Max: 60.00

Defines time constant for PID feedback filter.

r2266

CO: PID filtered feedback

Min: -

Datatype: Float Unit:

%

Def:

-

P-Group: TECH

Max: -

Displays PID feedback signal in [%].

Note:

r2266 = 100 % corresponds to 4000 hex

Level

3

Level

3

Level

3

Level

2

Level

2

Level

2

Advertising