Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

200

6SE6400-5BB00-0BP0

r2018[8]

CO: PZD from COM link (USS)

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: COMM

Max: -

Displays process data received via USS on COM link.

.

.

.

r2037

r2036

[0]

r2018

[1]
[2]
[3]

[7]

STX
LGE
ADR

Start of text
Length
Address

PKW
PZD
BCC

Parameter ID value
Process data
Block check character

PZD mapping to parameter r2018

STW

HSW

Control word

Main setpoint

USS on COM link

PZD1

STW1

PZD2

HSW

PZD3

PZD4

STW2

P2012

USS telegram

STX

LGE

ADR

BCC

PKW

PZD

Process data

Parameter

Index:

r2018[0] : Received word 0
r2018[1] : Received word 1
r2018[2] : Received word 2
r2018[3] : Received word 3
r2018[4] : Received word 4
r2018[5] : Received word 5
r2018[6] : Received word 6
r2018[7] : Received word 7

Note:

The control words can be viewed as bit parameters r2036 and r2037.

Restrictions:
-

If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be
transferred in the 1st PZD-word.

-

If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the
2nd PZD-word,

-

When P2012 is greater than or equal to 4 the additional control word (2nd control word) must
transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).