6SE6400-5BB00-0BP0

P0821

BI: DDS bit 1

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4095:0

Selects command source from which Bit 1 for selecting a drive data set is to be read in (see parameter
P0820).

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)

Note:

P0820 is also relevant for drive data set (DDS) selection.

3.14 BICO

command

parameters

P0840[3] BI:

ON/OFF1

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

722:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Allows ON/OFF1 command source to be selected using BICO.

The first three digits describe the parameter number of the command source; the last digit denotes the bit
setting for that parameter. The default setting (ON right) is digital input 1 (722.0). Alternative source possible
only when function of digital input 1 is changed (via P0701) before changing value of P0840.

f

t

f max

(P1082)

f

2

0

P1082

f

P1121

t

2

1

OFF

,

down

=

P2167

P1121

t

down,OFF1

OFF1

P2168

ON

P1120

r0052 Bit02

Operation

Pulse

cancellation

t

t

P2168

f

act,motor

f

act,inverter

Index:

P0840[0] : 1st. Command data set (CDS)
P0840[1] : 2nd. Command data set (CDS)
P0840[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.0 = ON/OFF1 via BOP

Dependency:

Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

Note:

-

OFF1 means a ramp stop down to 0 using P1121.

-

OFF1 is low active.

-

For the priority of all soft commands, the following applies: OFF2, OFF3, OFF1