Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

196

6SE6400-5BB00-0BP0

P2012[2]

USS PZD length

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

2

P-Group: COMM

Active: first confirm

QuickComm.: No

Max: 8

Defines the number of 16-bit words in PZD part of USS telegram.

Index:

P2012[0] : Serial interface COM link
P2012[1] : Serial interface BOP link

Notice:

USS protocol consists of PZD and PKW which can be changed by the user via parameters P2012 and
P2013 respectively.

PKE

IND

PWE

STX
LGE
ADR

STX

LGE ADR

BCC

PZD1

PZD2

PZD3

PZD4

PKE
IND
PWE

Parameter ID

Sub-index
Parameter value

PKW

PZD

PKW
PZD
BCC

Start of text
Length
Address
Parameter ID value
Process data
Block check character

Process data

Parameter

USS telegram


PZD transmits a control word and setpoint or status word and actual values. The number of PZD-words in a
USS-telegram are determined by parameter P2012, where the first two words (P2012 >= 2) are either:
-

control word and main setpoint or

-

status word and actual value.


Restrictions:
-

If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be
transferred in the 1st PZD-word.

-

If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the
2nd PZD-word,

-

When P2012 is greater than or equal to 4 the additional control word (2nd control word) must
transferred in the 4th PZD-word, if the serial interface controls the inverter (P0700 or P0719).

STW
ZSW

STW
ZSW
PZD

Control word
Status word
Process data

STW2

HSW
HIW

Main setpoint

Main actual value

HSW

HIW

P2012

PZD1

PZD2

PZD3

PZD4