4 torque control – Siemens 440 User Manual

Page 173

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

173

3.29.2.4 Torque

control

P1500[3]

Selection of torque setpoint

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: CONTROL

Active: first confirm

QuickComm.: Yes Max: 77

Selects torque setpoint source. In the table of possible settings below, the main setpoint is selected from the
least significant digit (i.e., 0 to 7) and any additional setpoint from the most significant digit (i.e., x0 through
to x7).

Possible Settings:

0

No main setpoint

2 Analog

setpoint

4

USS on BOP link

5

USS on COM link

6

CB on COM link

7

Analog setpoint 2

20 No main setpoint + Analog setpoint
22 Analog setpoint

+ Analog setpoint

24 USS on BOP link + Analog setpoint
25 USS on COM link + Analog setpoint
26 CB on COM link + Analog setpoint
27 Analog setpoint 2 + Analog setpoint
40 No main setpoint + USS on BOP link
42 Analog setpoint

+ USS on BOP link

44 USS on BOP link + USS on BOP link
45 USS on COM link + USS on BOP link
46 CB on COM link + USS on BOP link
47 Analog setpoint 2 + USS on BOP link
50 No main setpoint + USS on COM link
52 Analog setpoint

+ USS on COM link

54 USS on BOP link + USS on COM link
55 USS on COM link + USS on COM link
57 Analog setpoint 2 + USS on COM link
60 No main setpoint + CB on COM link
62 Analog setpoint

+ CB on COM link

64 USS on BOP link + CB on COM link
66 CB on COM link + CB on COM link
67 Analog setpoint 2 + CB on COM link
70 No main setpoint + Analog setpoint 2
72 Analog setpoint

+ Analog setpoint 2

74 USS on BOP link + Analog setpoint 2
75 USS on COM link + Analog setpoint 2
76 CB on COM link + Analog setpoint 2
77 Analog setpoint 2 + Analog setpoint 2

Index:

P1500[0] : 1st. Command data set (CDS)
P1500[1] : 2nd. Command data set (CDS)
P1500[2] : 3rd. Command data set (CDS)

Example:

Setting 24 selects the main setpoint (4) derived from the USS on BOP link with the additional setpoint (2)
derived from the analog input. Single digits are main setpoints only with no additional setpoint.

P1500 =

2

4

⇒ P1503 = 755.0

P1503 CI: Torque setpoint

r0755 CO: Act. ADC after scal. [4000h]

P1500 = 2

4

⇒ P1511 = r2015.1

P1511 CI: Additional torque setpoint

r2015 CO: PZD from BOP link (USS)

Example P1500 = 24 :

ADC

USS

BOP link

USS

COM link

CB

COM link

ADC2

P1000 =

2

4

Additonal

torque setpoint

P1000 = 2

4

Torque

control

Sequence

control

Torque

setpoint

Level

2