Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

34

6SE6400-5BB00-0BP0

r0052

CO/BO: Act. status word 1

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: COMMANDS

Max: -

Displays first active status word of inverter (bit format) and can be used to diagnose inverter status.

Bitfields:

Bit00 Drive ready 0 NO 1 YES
Bit01 Drive ready to run 0 NO 1 YES
Bit02 Drive running 0 NO 1 YES
Bit03 Drive fault active 0 NO 1 YES

Bit04 OFF2 active 0 YES 1 NO
Bit05 OFF3 active 0 YES 1 NO
Bit06 ON inhibit active 0 NO 1 YES
Bit07 Drive warning active 0 NO 1 YES

Bit08 Deviation setpoint / act. value 0 YES 1 NO
Bit09 PZD control 0 NO 1 YES
Bit10 Maximum frequency reached 0 NO 1 YES
Bit11 Warning: Motor current limit 0 YES 1 NO

Bit12 Motor holding brake active 0 NO 1 YES
Bit13 Motor overload 0 YES 1 NO
Bit14 Motor runs right 0 NO 1 YES
Bit15 Inverter overload 0 YES 1 NO

Dependency:

t

0

Power ON

t

r0052

Bit00

Drive ready

1

0

1

t

ON/OFF1

0

1

t

0

1

t

r0052

Bit01

Drive ready to run

0

1

t

Pulse enable

0

1

t

r0052
Bit02

Drive running

0

1

t

r0053
Bit09

0

1

Pre-charging active

Ramping finished

r0052 Bit00 - Bit02:
State-sequence diagram after Power On or ON/OFF1 respectively: ==> see below


r0052 Bit03 "Drive fault active":
Output of Bit3 (Fault) will be inverted on digital output (Low = Fault, High = No Fault).

r0052 Bit08 "Deviation setpoint / act. value" ==> see parameter P2164

r0052 Bit10 "f_act >= P1082 (f_max)" ==> see parameter P1082

r0052 Bit12 "Motor holding brake active" ==> see parameter P1215