9 motor model – Siemens 440 User Manual

Page 183

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

183

r1725

CO: Integral limit of Isd ctrl.

Min: -

Datatype: Float Unit:

V

Def:

-

P-Group: CONTROL

Max: -

Displays limit of integral output voltage setpoint of Isd current controller.

r1728 CO:

Decoupling

voltage

Min: -

Datatype: Float Unit:

V

Def:

-

P-Group: CONTROL

Max: -

Displays actual output voltage setpoint of cross channel decoupling.

P1740

Gain for oscillation damping

Min: 0.000

CStat:

CUT

Datatype: Float Unit:

-

Def:

0.000

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 10.000

Sets the controller gain to dampen oscillations in the sensorless vector control (SLVC) at low frequencies
(open-loop).

P1740

T

1740

P

f

i

sq

-

res damping

Dependency:

Siehe P1750, P1755, P1756

P1745[3]

Variance flux error

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

5.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 1000.0

Allowed variance error between flux setpoint and measured flux.

Index:

P1745[0] : 1st. Drive data set (DDS)
P1745[1] : 2nd. Drive data set (DDS)
P1745[2] : 3rd. Drive data set (DDS)

r1746

CO: Variance flux error

Min: -

Datatype: Float Unit:

%

Def:

-

P-Group: CONTROL

Max: -

Variance error between flux setpoint and measured flux.

3.29.2.9 Motor

model

P1750[3]

Control word of motor model

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: CONTROL

Active: first confirm

QuickComm.: No

Max: 3

Control word of motor model. This parameter controls the operation of the sensorless vector control (SLVC)
at very low frequencies. This therefore includes the following conditions:
-

Operation directly after an ON command

- zero

crossing.

f

t

P1755

Closed loop

Open loop

Start

f

t

Closed loop

Open loop

Zero crossing

P1755

P1755

Level

4

Level

4

Level

3

Level

3

Level

3

Level

3

Advertising