Parameter description issue 01/06, P2257 ramp-up time for pid setpoint, P2258 ramp-down time for pid setpoint – Siemens 440 User Manual

Page 234: R2260 co: pid setpoint after pid-rfg

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

234

6SE6400-5BB00-0BP0

P2257

Ramp-up time for PID setpoint

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

s

Def:

1.00

P-Group: TECH

Active: Immediately

QuickComm.: No

Max: 650.00

Sets the ramp-up time for the PID setpoint.

PID Setpoint (%)

0

100 %

t (s)

x

2

x

1

P2257

t

12

P2257

%

100

x

x

t

1

2

12

=

Dependency:

P2200 = 1 (PID control is enabled) disables normal ramp-up time (P1120).

PID ramp time effective only on PID setpoint and only active
-

when PID setpoint is changed or

-

when RUN command is given.

Notice:

Setting the ramp-up time too short may cause the inverter to trip, on overcurrent for example.

P2258

Ramp-down time for PID setpoint

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

s

Def:

1.00

P-Group: TECH

Active: Immediately

QuickComm.: No

Max: 650.00

Sets ramp-down time for PID setpoint.

PID Setpoint (%)

0

100 %

t (s)

x

2

x

1

P2258

t

21

P2258

%

100

x

x

t

2

1

21

=

Dependency:

-

P2200 = 1 (PID control is enabled) disables normal ramp-up time (P1120).

-

PID setpoint ramp effective only on PID setpoint changes.

-

P1121 (ramp-down time) and P1135 (OFF3 ramp-down time) define the ramp times used after OFF1
and OFF3 respectively.

Notice:

Setting the ramp-down time too short can cause the inverter to trip on overvoltage (F0002) / overcurrent
(F0001).

r2260

CO: PID setpoint after PID-RFG

Min: -

Datatype: Float Unit:

%

Def:

-

P-Group: TECH

Max: -

Displays total active PID setpoint after PID-RFG in [%].

Note:

r2260 = 100 % corresponds to 4000 hex

Level

2

Level

2

Level

2

Advertising