20 setpoint channel – Siemens 440 User Manual

Page 125

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

125

3.20 Setpoint

channel

P1070[3]

CI: Main setpoint

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

755:0

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of main setpoint.

Index:

P1070[0] : 1st. Command data set (CDS)
P1070[1] : 2nd. Command data set (CDS)
P1070[2] : 3rd. Command data set (CDS)

Common Settings:

755 = Analog input 1 setpoint
1024 = Fixed frequency setpoint
1050 = Motor potentiometer (MOP) setpoint

P1071[3]

CI: Main setpoint scaling

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

1:0

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of the main setpoint scaling.

Index:

P1071[0] : 1st. Command data set (CDS)
P1071[1] : 2nd. Command data set (CDS)
P1071[2] : 3rd. Command data set (CDS)

Common Settings:

755 = Analog input 1 setpoint
1024 = Fixed frequency setpoint
1050 = Motor potentiometer (MOP) setpoint

P1074[3]

BI: Disable additional setpoint

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Disables additional setpoint

Index:

P1074[0] : 1st. Command data set (CDS)
P1074[1] : 2nd. Command data set (CDS)
P1074[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99))

P1075[3]

CI: Additional setpoint

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of the additional setpoint (to be added to main setpoint).

Index:

P1075[0] : 1st. Command data set (CDS)
P1075[1] : 2nd. Command data set (CDS)
P1075[2] : 3rd. Command data set (CDS)

Common Settings:

755 = Analog input 1 setpoint
1024 = Fixed frequency setpoint
1050 = Motor potentiometer (MOP) setpoint





Level

3

Level

3

Level

3

Level

3

Advertising