10 digital outputs, Parameter description issue 01/06, R0730 number of digital outputs – Siemens 440 User Manual

Page 84

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

84

6SE6400-5BB00-0BP0

3.10 Digital

outputs

r0730

Number of digital outputs

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: COMMANDS

Max: -

Displays number of digital outputs (relays).

P0731[3]

BI: Function of digital output 1

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

52:3

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of digital output 1.

(52:3)

BI: Fct. of DOUT 1

P0731.C

-1

0

1

Invert DOUTs

0 ... 7

P0748 (0)

CO/BO: State DOUTs

r0747

r0747

Kl.20

Kl.18

.0

Function

xxxx .y

rxxxx.y

P0731 = xxxx.y

DOUT channel

Relay :

DC 30 V / 5 A
AC 250 V / 2 A

Kl.28

Kl.9

int. 24 V
max. 100 mA

NO

COM

NC

Kl.19

or

max. load capability

max. opening / closing time

5 / 10 ms

Index:

P0731[0] : 1st. Command data set (CDS)
P0731[1] : 2nd. Command data set (CDS)
P0731[2] : 3rd. Command data set (CDS)

Common Settings:

52.0

Drive ready

0 Closed

52.1

Drive ready to run

0 Closed

52.2

Drive running

0 Closed

52.3

Drive fault active

0 Closed

52.4

OFF2 active

1 Closed

52.5

OFF3 active

1 Closed

52.6

Switch on inhibit active

0 Closed

52.7

Drive warning active

0 Closed

52.8

Deviation setpoint/actual value

1 Closed

52.9

PZD control (Process Data Control)

0 Closed

52.A

Maximum frequency reached

0 Closed

52.B

Warning: Motor current limit

1 Closed

52.C

Motor holding brake (MHB) active

0 Closed

52.D

Motor overload

1 Closed

52.E

Motor running direction right

0 Closed

52.F

Inverter overload

1 Closed

53.0

DC brake active

0 Closed

53.1

Act. freq. f_act > P2167 (f_off)

0 Closed

53.2

Act. freq. f_act <= P1080 (f_min)

0 Closed

53.3

Act. current r0027 > P2170

0 Closed

53.4

Act. freq. f_act > P2155 (f_1)

0 Closed

53.5

Act. freq. f_act <= P2155 (f_1)

0 Closed

53.6

Act. freq. f_act >= setpoint

0 Closed

53.7

Act. Vdc r0026 < P2172

0 Closed

53.8

Act. Vdc r0026 > P2172

0 Closed

53.A

PID output r2294 == P2292 (PID_min) 0 Closed

53.B

PID output r2294 == P2291 (PID_max) 0 Closed

Details:

Display functions ==> see parameter r0052, r0053
Motor holding brake ==> see parameter P1215
DC brake ==> see parameter P1232, P1233

Level

3

Level

2

Advertising