Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

166

6SE6400-5BB00-0BP0

3.29.1.4 Soft

starting

P1350[3] Voltage

soft

start

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: CONTROL

Active: first confirm

QuickComm.: No

Max: 1

Selecting the soft starting function.

With soft starting, the flux in the motor is established with some delay. This ensures that the motor only
rotates in the required direction of rotation even with existing residual magnetism. When activated, at
powered-on, the output voltage is ramped-up to the value of the characteristic voltage within the
magnetizing time P0346.

f

V

t

1

P0346

P1350 P0346

V/f characteristic

Softstart

V

f

f

Possible Settings:

0 OFF
1 ON

Index:

P1350[0] : 1st. Drive data set (DDS)
P1350[1] : 2nd. Drive data set (DDS)
P1350[2] : 3rd. Drive data set (DDS)

Note:

The settings for this parameter bring benefits and drawbacks:
-

P1350 = 0: (jump to boost voltage)

Benefit: flux is built up quickly

Drawback: motor may move

-

P1350 = 1: (smooth voltage build-up)

Benefit: motor less likely to move

Drawback: flux build-up takes longer

Level

3