Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

55

r0332[3]

Rated power factor

Min: -

Datatype: Float Unit:

-

Def:

-

P-Group: MOTOR

Max: -

Displays power factor for motor

Index:

r0332[0] : 1st. Drive data set (DDS)
r0332[1] : 2nd. Drive data set (DDS)
r0332[2] : 3rd. Drive data set (DDS)

Dependency:

Value is calculated internally if P0308 (rated motor cosPhi) set to 0; otherwise, value entered in P0308 is
displayed.

r0333[3]

Rated motor torque

Min: -

Datatype: Float Unit:

Nm

Def:

-

P-Group: MOTOR

Max: -

Displays rated motor torque.

Index:

r0333[0] : 1st. Drive data set (DDS)
r0333[1] : 2nd. Drive data set (DDS)
r0333[2] : 3rd. Drive data set (DDS)

Dependency:

Value is calculated from P0307 (rated motor power) and P0311 (rated motor speed).

2

60

[1/min]

P0311

1000

[kW]

P0307

[Nm]

r0333

=

π

P0335[3] Motor

cooling

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: MOTOR

Active: first confirm

QuickComm.: Yes Max: 3

Selects motor cooling system used.

Possible Settings:

0

Self-cooled: Using shaft mounted fan attached to motor

1

Force-cooled: Using separately powered cooling fan

2

Self-cooled and internal fan

3

Force-cooled and internal fan

Index:

P0335[0] : 1st. Drive data set (DDS)
P0335[1] : 2nd. Drive data set (DDS)
P0335[2] : 3rd. Drive data set (DDS)

Caution:

The following combination of parameter setting should not be combined:
-

P0610 = 1 and P0335 = 0 or 2 :

When P0335 = 0 or 2 the inverter cools the motor using a shaft mounted fan. If this is used in
conjunction with P0610 the cooling of the motor will be inefficient.

In essence, if the i2t calculation reduces the output frequency, then the shaft mounted fan will also reduce
its cooling effect, the motor will then eventually overheat and trip.
- Exception:

Applications with variable torque the reduction of max. current leeds automatically to a reduction of the
load / output current.

Notice:

Motors of series 1LA1 and 1LA8 have an internal fan. This internal motor fan must not be confused with the
fan at the end of the motor shaft.

Level

3

Level

3

Level

2