Siemens 440 User Manual

Page 178

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

178

6SE6400-5BB00-0BP0

r1527

CO: Lower torque limitation

Min: -

Datatype: Float Unit:

Nm

Def:

-

P-Group: CONTROL

Max: -

Displays actual lower torque limitation.

Details:

See parameter r1526.

P1530[3]

Motoring power limitation

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

-

Def:

0.12

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 8000.00

Defines fixed value for the max. permissible motoring active power (motoring power limitation).

P1530

def

P1530

max

0307

P

3

=

0307

P

5

.

2

=


Parameter P1530 limits the torque in addition to the act. frequency as displayed in the following
characteristic.

M

f

f

2

P

M

π

=

Power limitation (motoring, regenerative)

P1530

P1531

P1530

P1531

Index:

P1530[0] : 1st. Drive data set (DDS)
P1530[1] : 2nd. Drive data set (DDS)
P1530[2] : 3rd. Drive data set (DDS)

P1531[3]

Regenerative power limitation

Min: -8000.00

CStat:

CUT

Datatype: Float Unit:

-

Def:

-0.12

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 0.00

Enters fixed value for the max. permissible regenerative active power (regenerative power limitation).

P1531

max

P0307

3

-

=

P1531

def

P0307

2.5

-

=

Index:

P1531[0] : 1st. Drive data set (DDS)
P1531[1] : 2nd. Drive data set (DDS)
P1531[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1530.

r1536

CO: Max. trq. motoring current

Min: -

Datatype: Float Unit:

A

Def:

-

P-Group: CONTROL

Max: -

Displays maximum torque motoring current component.

r1537

CO: Max trq regenerative current

Min: -

Datatype: Float Unit:

A

Def:

-

P-Group: CONTROL

Max: -

Displays maximum torque of the regenerative current component.

Level

3

Level

2

Level

2

Level

4

Level

4

Advertising