5.2 Alarm

Messages

Alarm messages are stored in parameter r2110 under their code number (e.g. A0503
= 503) and can be read out from there.

A0501 Current limit value

Cause

-

the motor power rating does not correspond to the inverter power rating

-

motor cables are too long

- ground

fault

Diagnosis & Remedy

Please check the following:
-

does the motor power rating (P0307) match the inverter power rating (r0206) ?

-

are the limit values for the cable lengths maintained ?

-

does the motor cable or motor have a short-circuit or ground fault ?

-

do the motor parameters correspond to those of the motor being used ?

-

stator resistance value (P0350) correct ?

-

is the motor overloaded or is the rotor locked (cannot rotate) ?

-

ramp-up time P1120 too low ?

A0502 Overvoltage limit value

Cause

-

the overvoltage limit value has been reached (actual value of the DC link voltage r0026 greater than
r1242).

Diagnosis & Remedy

-

if this alarm is permanently displayed, check the inverter input voltage.

-

is the DC link voltage controller (Vdc_max controller) de-activated (refer to parameter P1240) ?

-

short ramp times and/or large flywheel masses (moment of inertia) ?

A0503 Undervoltage limit value

Cause

-

line supply has failed.

-

line voltage and therefore also the DC link voltage (r0026) below the defined limit value (refer to
parameter r0026).

Diagnosis & Remedy

-

check the line voltage.

A0504 Inverter

overtemperature

Cause

-

alarm threshold of the inverter heatsink temperature (P0614) was exceeded; this results in a reduction
of the pulse frequency and/or the output frequency (dependent on the parameterization in (P0610).

Diagnosis & Remedy

Please check the following:
-

is the ambient temperature within the permissible limits ?

-

are the load and load duty cycle within the permissible limits ?

A0505 Inverter

I2T

Cause

-

overload alarm limit P0294 is exceeded (refer to utilization r0036)

-

the pulse frequency and/or the output frequency is reduced as a function of the setting of parameter
P0290.

Diagnosis & Remedy

-

check whether the load duty cycle lies within the permissible limits.

A0506 Inverter load duty cycle

Cause

-

difference between the temperature at the heatsink and IGBT exceeds the alarm limit values.

Diagnosis & Remedy

-

please ensure that the load duty cycle and load surge lie within the permissible limits.