Siemens 440 User Manual

Page 216

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

216

6SE6400-5BB00-0BP0

P2172[3]

Threshold DC-link voltage

Min: 0

CStat:

CUT

Datatype: U16 Unit:

V

Def:

800

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 2000

Defines DC link voltage to be compared to actual voltage as illustrated in the diagram below.

V

dc

t

0

1

0

1

P2173

t

t

r0053

Bit07

r0053
Bit08

P2172

P2173

V

dc_act

< P2172

V

dc_act

> P2172

Index:

P2172[0] : 1st. Drive data set (DDS)
P2172[1] : 2nd. Drive data set (DDS)
P2172[2] : 3rd. Drive data set (DDS)

Note:

This voltage controls bits 7 and 8 in status word 3 (r0053).

P2173[3]

Delay time DC-link voltage

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

10

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10000

Defines delay time prior to activation of threshold comparison.

Index:

P2173[0] : 1st. Drive data set (DDS)
P2173[1] : 2nd. Drive data set (DDS)
P2173[2] : 3rd. Drive data set (DDS)

Details:

See diagram in P2172 (threshold DC-link voltage)

Level

3

Level

3

Advertising