F0054 incorrect i/o module stop ii, F0060 asic time slice overflow stop ii, F0070 cb setpoint fault stop ii – Siemens 440 User Manual

Page 312: F0071 uss(bop link) setpoint fault stop ii, F0072 uss(comm link) setpoint fault stop ii, F0080 adc input signal lost stop ii, F0085 external fault stop ii

Advertising
background image

Faults and Alarms

Issue 01/06

MICROMASTER 440 Parameter List

312

6SE6400-5BB00-0BP0

F0054 Incorrect I/O module

STOP II

Quit

Refer to F0001

Cause

-

incorrect I/O module inserted.

-

no ID of the I/O module found, no data.

Diagnosis & Remedy

Please check the following:
-

check I/O data, if required repeat the operation

-

the installation of the I/O module in the inverter if required, replace the I/O module

F0060 Asic time slice overflow

STOP II

Quit

Refer to F0001

Cause

-

internal communications failure/error

Diagnosis & Remedy

-

if the error still occurs, replace the inverter.

-

contact customer service!

F0070 CB setpoint fault

STOP II

Quit

Refer to F0001

Cause

-

no setpoints received via the communications bus during the telegram failure time.

Diagnosis & Remedy

-

check the communications module (CB) and communications partner.

F0071 USS(BOP link) setpoint fault

STOP II

Quit

Refer to F0001

Cause

-

no setpoint was received via the USS during the telegram off time

Diagnosis & Remedy

-

check USS master

F0072 USS(COMM link) setpoint fault

STOP II

Quit

Refer to F0001

Cause

-

no setpoints received via the USS during the telegram off time

Diagnosis & Remedy

-

check USS master

F0080 ADC input signal lost

STOP II

Quit

Refer to F0001

Cause

- wire

breakage

-

signal outside the limit values

F0085 External fault

STOP II

Quit

Refer to F0001

Cause

-

external fault as a result of command input via terminals.

Diagnosis & Remedy

-

inhibit terminal input to initiate fault.