Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

164

6SE6400-5BB00-0BP0

3.29.1.3 Imax

controller

P1340[3]

Imax freq. controller prop. gain

Min: 0.000

CStat:

CUT

Datatype: Float Unit:

-

Def:

0.000

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 0.499

Proportional gain of the I_max frequency controller.

The Imax controller reduces inverter current if the output current exceeds the maximum motor current
(r0067).

In linear V/f, parabolic V/f, FCC, and programmable V/f modes the I_max controller uses both a frequency
controller (see parameters P1340 and P1341) and a voltage controller (see parameters P1345 and P1346).
The frequency controller seeks to reduce current by limiting the inverter output frequency (to a minimum of
the two times nominal slip frequency). If this action does not successfully remove the overcurrent condition,
the inverter output voltage is reduced using the I_max voltage controller. When the overcurrent condition
has been removed successfully, frequency limiting is removed using the ramp-up time set in P1120.

t

t

f

1

-controller active

I

max

t

r0067

0

r0056 Bit13

A0501

Motor current


In linear V/f for textiles, FCC for textiles, or external V/f modes only the I_max voltage controller is used to
reduce current (See parameters P1345 and P1346).

Index:

P1340[0] : 1st. Drive data set (DDS)
P1340[1] : 2nd. Drive data set (DDS)
P1340[2] : 3rd. Drive data set (DDS)

Note:

The I_max controller can be disabled by setting the frequency controller integral time P1341 to zero. This
disables both the frequency and voltage controllers. Note that when disabled, the I_max controller will take
no action to reduce current but overcurrent warnings will still be generated, and the Drive will trip in
excessive overcurrent or overload conditions.

P1341[3]

Imax freq. ctrl. integral time

Min: 0.000

CStat:

CUT

Datatype: Float Unit:

s

Def:

0.300

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 50.000

Integral time constant of the I_max controller.

P1341 = 0 :
I_max frequency and voltage controllers disabled

P1340 = 0 and P1341 > 0 :
frequency controller enhanced integral

P1340 > 0 and P1341 > 0 :
frequency controller normal PI control

See description in parameter P1340 for further information.

Index:

P1341[0] : 1st. Drive data set (DDS)
P1341[1] : 2nd. Drive data set (DDS)
P1341[2] : 3rd. Drive data set (DDS)

Level

3

Level

3