Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

152

6SE6400-5BB00-0BP0

P1256 = 1:
Maintain dclink voltage until mains is returned or drive is tripped undervoltage or pulses disabled when
frequency falls below the limit in P1257.

P1245

t

0

1

V

DC

t

t

f

V

DC_min

P1257

Pulse

enabled


P1256 = 2:
This option ramps down the frequency to stand still even when mains return. If mains return, then an OFF1
is active until P1257 limit then pulses disabled. If mains does not return, frequency brought down under the
control of vdc-min controller until P1257 limit then pulses disabled or undervoltage has occurred.

P1245

t

0

1

V

DC

t

t

f

V

DC_min

P1257

OFF1

OFF2

Pulse

enabled

P1257[3]

Freq limit for kinetic buffering

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

2.50

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 600.00

Frequency which kinetic buffering (KIB) either hold speed or disable pulses depending on P1256.

Index:

P1257[0] : 1st. Drive data set (DDS)
P1257[1] : 2nd. Drive data set (DDS)
P1257[2] : 3rd. Drive data set (DDS)

Level

3