7 flux control, Issue 01/06 parameter description, R1538 co: upper torque limit (total) – Siemens 440 User Manual

Page 179: R1539 co: lower torque limit (total)

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

179

r1538

CO: Upper torque limit (total)

Min: -

Datatype: Float Unit:

Nm

Def:

-

P-Group: CONTROL

Max: -

Displays total upper torque limitation.

P1530

Motoring power lim

Current

controller

Speed controller

or

Torque controller

CO: Lower trq. lim

r1538

CO:Total up TrqLim [Nm]

r0079

CO: Total trq setp [Nm]

r0067

CO: Outp cur limit [A]

CI: Add. trq. setp

(0:0)

P1511.C

Torque limitation

Torque limitation :

P1521

P1520

CI: Upper trq. lim

(1520:0)

P1522.C

CI: Lower trq. lim

(1521:0)

P1523.C

P0640

Motor ovl fact [%]

Motor / inverter

protection

P0305

Rated mot. current

Max. inverter cur [A]
r0209

CO: Upper trq. lim

P1525

Scal. low trq. lim

P1531

Regener. power lim

r1539

CO:Total lw TrqLim [Nm]

r1526

CO: Upper trq. lim [Nm]

r1527

CO: Lower trq. lim [Nm]

r1539

CO: Lower torque limit (total)

Min: -

Datatype: Float Unit:

Nm

Def:

-

P-Group: CONTROL

Max: -

Displays total lower torque limitation.

Details:

See parameter r1538.

3.29.2.7 Flux

control

P1570[3]

CO: Fixed value flux setpoint

Min: 50.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

107.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 200.0

Parameter to set the flux setpoint as a % relative to the rated motor flux.

Index:

P1570[0] : 1st. Drive data set (DDS)
P1570[1] : 2nd. Drive data set (DDS)
P1570[2] : 3rd. Drive data set (DDS)

Note:

-

In the base speed range, the flux setpoint P1570 is converted into the field-generating current
component isd (P1570 = 100% corresponds to r0331).

-

For values below 100%, the drive is under-magnetized and above this, is over-magnetized.

-

If P1570 is set to more than 100%, then the flux setpoint, depending on the load, is increased from
100% (under no-load conditions) to this value (under rated load, refer to the diagram).

-

If in so doing, the maximum drive inverter output voltage is reached, the rotor flux is reduced in order to
keep the output voltage constant (or the EMF) with increasing speed.

-

The maximum possible output voltage r0071 of the drive inverter is determined by the DC link voltage
r0026 and the maximum modulation depth P1803 in the gating unit.

P1570

i

N,Motor

i

Motor

Ψ

Ψ

N

set

(100 %)

Field weakening

f

Ψ

i

N,Motor

i

Motor

Level

2

Level

2

Level

2