Siemens 440 User Manual

Page 138

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

138

6SE6400-5BB00-0BP0

r1204

Status word: Flying start V/f

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: FUNC

Max: -

Bit parameter for checking and monitoring states during search, if V/f control mode is selected (see P1300).

Bitfields:

Bit00 Current applied 0 NO 1 YES
Bit01 Current could not be applied 0 NO 1 YES
Bit02 Voltage reduced 0 NO 1 YES
Bit03 Slope-filter started 0 NO 1 YES

Bit04 Current less threshold 0 NO 1 YES
Bit05 Current-minimum 0 NO 1 YES
Bit07 Speed could not be found 0 NO 1 YES

r1205

Status word: Flying start SLVC

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: FUNC

Max: -

Bit parameter for checking status of flying start performed with n-adaption of observer. Parameter is only
valid, if sensorless vector control (SLVC) is selected (see P1300).

Bitfields:

Bit00 Transformation active 0 NO 1 YES
Bit01 Initialize n-adaption 0 NO 1 YES
Bit02 Current applying 0 NO 1 YES
Bit03 N-controller closed 0 NO 1 YES

Bit04 Isd-controller open 0 NO 1 YES
Bit05 RFG hold 0 NO 1 YES
Bit06 N-adaption set to zero 0 NO 1 YES
Bit07 Reserved 0 NO 1 YES

Bit08 Reserved 0 NO 1 YES
Bit09 Reserved 0 NO 1 YES
Bit10 Direction Positive 0 NO 1 YES
Bit11 Search is started 0 NO 1 YES

Bit12 Current is applied 0 NO 1 YES
Bit13 Search is aborted 0 NO 1 YES
Bit14 Deviation is zero 0 NO 1 YES
Bit15 N-controller is active 0 NO 1 YES

Level

4

Level

3

Advertising