Parameter description issue 01/06 – Siemens 440 User Manual

Page 60

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

60

6SE6400-5BB00-0BP0

P0352[3] Cable

resistance

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

Ohm

Def:

0.0

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 120.0

Describes cable resistance between inverter and motor for one phase.

d

M

l

l : Cable length

d : Cable diameter

A : Cable cross-section

: Specific resistance

ρ

A

l

R

ρ

=

2

2

d

A





π

=

m

mm

0,0178

2

Cu

=

ρ

Inverter

Index:

P0352[0] : 1st. Drive data set (DDS)
P0352[1] : 2nd. Drive data set (DDS)
P0352[2] : 3rd. Drive data set (DDS)

P0354[3] Rotor

resistance

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

Ohm

Def:

10.0

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 300.0

Sets rotor resistance of motor equivalent circuit (phase value).

Index:

P0354[0] : 1st. Drive data set (DDS)
P0354[1] : 2nd. Drive data set (DDS)
P0354[2] : 3rd. Drive data set (DDS)

Dependency:

Calculated automatically using the motor model or determined using P1910 (motor identification).

P0356[3]

Stator leakage inductance

Min: 0.00001

CStat:

CUT

Datatype: Float Unit:

-

Def:

10.00000

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 1000.00000

Sets stator leakage inductance [mH] of motor equivalent circuit (phase value).

1000

0356

P

0310

P

2

L

f

2

L

X

S

S

S

π

=

π

=

ω

=

σ

σ

σ

Stator leakage reactance:

Index:

P0356[0] : 1st. Drive data set (DDS)
P0356[1] : 2nd. Drive data set (DDS)
P0356[2] : 3rd. Drive data set (DDS)

Dependency:

Calculated automatically using the motor model or determined using P1910 (motor identification).

P0358[3]

Rotor leakage inductance

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

-

Def:

10.0

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 1000.0

Sets rotor leakage inductance [mH] of motor equivalent circuit (phase value).

1000

0358

P

0310

P

2

L

f

2

L

X

R

R

R

π

=

π

=

ω

=

σ

σ

σ

Rotor leakage reactance:

Index:

P0358[0] : 1st. Drive data set (DDS)
P0358[1] : 2nd. Drive data set (DDS)
P0358[2] : 3rd. Drive data set (DDS)

Dependency:

Calculated automatically using the motor model or determined using P1910 (motor identification).

Level

3

Level

4

Level

4

Level

4

Advertising