12 analog outputs – Siemens 440 User Manual

Page 93

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

93

3.12 Analog

outputs

r0770

Number of DACs

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: TERMINAL

Max: -

Displays number of analog outputs available.

P0771[2] CI:

DAC

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

21:0

P-Group: TERMINAL

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines function of the 0 - 20 mA analog output.

Index:

P0771[0] : Analog output 1 (DAC 1)
P0771[1] : Analog output 2 (DAC 2)

Common Settings:

21 CO: Act. frequency (scaled to P2000)
24 CO: Act. output frequency (scaled to P2000)
25 CO: Act. output voltage (scaled to P2001)
26 CO: Act. filtered DC-link volt. (scaled to P2001)
27 CO: Act. output current (scaled to P2002)

DAC

scaling

P

0777

P

0778

P

0779

P

0780

DAC

dead

zone

r0774

P0781

P0773

DAC channel

Function

xxx

r0xxx

P0771

D

A

P0771 = xxx

P0773[2]

Smooth time DAC

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

2

P-Group: TERMINAL

Active: first confirm

QuickComm.: No

Max: 1000

Defines smoothing time [ms] for analog output signal. This parameter enables smoothing for DAC using a
PT1 filter.

Index:

P0773[0] : Analog output 1 (DAC 1)
P0773[1] : Analog output 2 (DAC 2)

Dependency:

P0773 = 0: Deactivates filter.

r0774[2]

Act. DAC value [mA]

Min: -

Datatype: Float Unit:

-

Def:

-

P-Group: TERMINAL

Max: -

Shows value of analog output in [mA] after filtering and scaling.

Index:

r0774[0] : Analog output 1 (DAC 1)
r0774[1] : Analog output 2 (DAC 2)

P0775[2]

Permit absolute value

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: TERMINAL

Active: first confirm

QuickComm.: No

Max: 1

Decides if the absolute value of the analog output is used. If enabled, this parameter will take the absolute
value of the value to be outputed. If the value was originally negative then the corresponding bit in R0783 is
set, otherwise it is cleared.

Possible Settings:

0 OFF
1 ON

Index:

P0775[0] : Analog output 1 (DAC 1)
P0775[1] : Analog output 2 (DAC 2)

Level

3

Level

2

Level

2

Level

2

Level

2

Advertising