Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

189

P1825

On-state voltage of IGBT

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

V

Def:

1.4

P-Group: INVERTER

Active: Immediately

QuickComm.: No

Max: 20.0

Corrects on-state voltage of the IGBTs.

P1828

Gating unit dead time

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

us

Def:

0.50

P-Group: INVERTER

Active: first confirm

QuickComm.: No

Max: 3.50

Sets compensation time of gating unit interlock.

3.31

Motor data identification

P1909[3]

Ctrl. word of motor data ident.

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

1

P-Group: CONTROL

Active: first confirm

QuickComm.: No

Max: 1

Control word of motor data identification.

Bitfields:

Bit00 Estimation of Xs 0 NO 1 YES

Index:

P1909[0] : 1st. Drive data set (DDS)
P1909[1] : 2nd. Drive data set (DDS)
P1909[2] : 3rd. Drive data set (DDS)

P1910

Select motor data identification

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: MOTOR

Active: first confirm

QuickComm.: Yes Max: 20

Performs a motor data identification.

Possible Settings:

0 Disabled
1

Identification of all parameters with parameter change

2

Identification of all parameters without parameter change

3

Identification of saturation curve with parameter change

4

Identification of saturation curve without parameter change

5

Identification of XsigDyn (r1920) without parameter change

6

Identification of Tdead (r1926) without parameter change

7

Identification of Rs (r1912 ) without parameter change

8

Identification of Xs (r1915) without parameter change

9

Identification of Tr (r1913) without parameter change

10 Identification of Xsigma (r1914) without parameter change
20 Set voltage vector

Common Settings:

P1910 = 1:

All motor data and inverter characteristic will be identified and parameter will be changed.
-

P0350 stator resistance,

-

P0354 rotor resistance,

-

P0356 stator leakage inductance,

-

P0358 rotor leakage inductance,

-

P0360 main inductance

-

P1825 on-state voltage of IGBTs

-

P1828 compensation time of gating unit interlock


P1910 = 3:

Saturation curve will be identified and parameter will be changed.
-

P0362 ... P0365 magnetizing curve flux 1 .. 4

-

P0366 ... P0369 magnetizing curve imag 1 .. 4

Caution:

Motor identification should normally be performed on a cold motor. However, the identification of the motor
data should only be performed if the motor temperature is within 5°C of the measured ambient temperature
stored in P0625. If the motor identification is not within the 5ºC limit then the correct functioning of Vector
Control (VC, SLVC) cannot be guaranteed. This may cause instabilities when using vector control.

The motor rating plate information with respect to the connection of the motor windings (Star or delta
connection) must be correct in order to establish the correct equivalent circuit data. The motor identification
calculates this data based on a Phase of a Star equivalent circuit P0350 - P0360, irrespective of whether
the motor is connected star or delta. This must be considered when the motor data is input directly.

Note:

-

In order to that the motor identification routine supplies the correct data, before selecting, fast
commissioning should be carried-out.

-

If the motor data identification routine is activated (e.g. P1910 = 1), then at the next ON command, the
measuring operation is started and alarm A0541 is generated. After the measurement is completed,
both P1910 and the alarm are reset.