Siemens 440 User Manual

Page 39

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

39

r0070

CO: Act. DC-link voltage

Min: -

Datatype: Float Unit:

V

Def:

-

P-Group: INVERTER

Max: -

Displays (unfiltered) DC-link voltage.

Note:

Used for process control purposes (in contrast to r0026 (actual DC-link voltage), which is filtered and is
used to display the value on the BOP/AOP).

r0071

CO: Max. output voltage

Min: -

Datatype: Float Unit:

V

Def:

-

P-Group: CONTROL

Max: -

Displays maximum output voltage.

V

max

= f(V

dc

,MOD

max

)

(Inverter)

(Motor)

r0071

V

max

Power

Field weakening

f

f

f

1

~

Flux

P,

Φ

P0304

V

n

P0310

f

n

V

(Motor)

(Inverter)

V

out

Dependency:

-

The actual maximum output voltage depends on the actual incoming line supply voltage.

-

The maximum possible output voltage r0071 of the drive inverter is determined by the DC link voltage
r0026 and the maximum modulation depth P1803 in the gating unit.

-

The maximum output voltage r0071 is tracked with the DC link voltage so that the highest possible
value is always and automatically achieved.

-

The output voltage only reaches the calculated maximum value under steady-state conditions at the
rated load.

-

In the no-load and partial load ranges, lower output voltages r0025 are obtained.

r0072

CO: Act. output voltage

Min: -

Datatype: Float Unit:

V

Def:

-

P-Group: CONTROL

Max: -

Displays output voltage.

r0074

CO: Act. modulation

Min: -

Datatype: Float Unit:

%

Def:

-

P-Group: CONTROL

Max: -

Displays actual modulation index.

The modulation index is defined as ratio between the magnitude of the fundamental component in the
inverter phase output voltage and half of the dc-link voltage.


Level

3

Level

3

Level

3

Level

4

Advertising