Siemens 440 User Manual

Page 117

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

117

P1017[3]

Fixed frequency mode - Bit 1

Min: 1

CStat:

CT

Datatype: U16 Unit:

-

Def:

1

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 3

Fixed frequencies can be selected in three different modes. Parameter P1017 defines the mode of selection
Bit 1.

Possible Settings:

1 Direct

selection

2

Direct selection + ON command

3

Binary coded selection + ON command

Index:

P1017[0] : 1st. Command data set (CDS)
P1017[1] : 2nd. Command data set (CDS)
P1017[2] : 3rd. Command data set (CDS)

Details:

See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.

P1018[3]

Fixed frequency mode - Bit 2

Min: 1

CStat:

CT

Datatype: U16 Unit:

-

Def:

1

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 3

Fixed frequencies can be selected in three different modes. Parameter P1018 defines the mode of selection
Bit 2.

Possible Settings:

1 Direct

selection

2

Direct selection + ON command

3

Binary coded selection + ON command

Index:

P1018[0] : 1st. Command data set (CDS)
P1018[1] : 2nd. Command data set (CDS)
P1018[2] : 3rd. Command data set (CDS)

Details:

See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.

P1019[3]

Fixed frequency mode - Bit 3

Min: 1

CStat:

CT

Datatype: U16 Unit:

-

Def:

1

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 3

Fixed frequencies can be selected in three different modes. Parameter P1019 defines the mode of selection
Bit 3.

Possible Settings:

1 Direct

selection

2

Direct selection + ON command

3

Binary coded selection + ON command

Index:

P1019[0] : 1st. Command data set (CDS)
P1019[1] : 2nd. Command data set (CDS)
P1019[2] : 3rd. Command data set (CDS)

Details:

See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.

P1020[3]

BI: Fixed freq. selection Bit 0

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines origin of fixed frequency selection.

Index:

P1020[0] : 1st. Command data set (CDS)
P1020[1] : 2nd. Command data set (CDS)
P1020[2] : 3rd. Command data set (CDS)

Common Settings:

P1020 = 722.0 ==> Digital input 1
P1021 = 722.1 ==> Digital input 2
P1022 = 722.2 ==> Digital input 3
P1023 = 722.3 ==> Digital input 4
P1026 = 722.4 ==> Digital input 5
P1028 = 722.5 ==> Digital input 6

Dependency:

Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)

Level

3

Level

3

Level

3

Level

3

Advertising