Siemens 440 User Manual

Page 123

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

123

P1058[3]

JOG frequency right

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

5.00

P-Group: SETPOINT

Active: Immediately

QuickComm.: No

Max: 650.00

Jogging increases the motor frequency by small amounts. The JOG buttons uses a non-latching switch on
one of the digital inputs to control the motor frequency.

If JOG clockwise (jogging clockwise) or JOG counter-clockwise is selected, the speed is increased until the
value, set in P1058 is reached.

JOG right

f

P1058

P1059

A0923

A0923

P

1060

P

1060

(0)

P1055

(0)

P1056

"1"

"0"

"1"

"0"

t

t

t

P

1061

DIN

BOP

USS

BOP link

USS

COM link

CB

COM link

JOG left

P1082

-P1082

P

1061

Index:

P1058[0] : 1st. Drive data set (DDS)
P1058[1] : 2nd. Drive data set (DDS)
P1058[2] : 3rd. Drive data set (DDS)

Dependency:

P1060 and P1061 set up and down ramp times respectively for jogging.

P1059[3]

JOG frequency left

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

5.00

P-Group: SETPOINT

Active: Immediately

QuickComm.: No

Max: 650.00

While JOG left is selected, this parameter determines the frequency at which the inverter will run.

Index:

P1059[0] : 1st. Drive data set (DDS)
P1059[1] : 2nd. Drive data set (DDS)
P1059[2] : 3rd. Drive data set (DDS)

Dependency:

P1060 and P1061 set up and down ramp times respectively for jogging.

Level

2

Level

2