Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

170

6SE6400-5BB00-0BP0

r1482

CO: Integral output of n-ctrl.

Min: -

Datatype: Float Unit:

Nm

Def:

-

P-Group: CONTROL

Max: -

Displays integral part of speed controller output.

3.29.2.2 Droop

P1488[3] Droop

input

source

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: CONTROL

Active: first confirm

QuickComm.: No

Max: 3

Selects source of droop input signal.

With mechanically coupled motors it is very important that an even load distribution is applied to each motor.
The load sharing can be achieved by enabling the droop function on both inverters.

Torque

setpoint

Act. frequency

Filter

r1538

r1539

Pre-

control

Freq. setpoint

Filter

PI

Speed

controller

Droop input source

0 ... 3

P1488.D (0)

Droop scaling

0.0 ... 0.50

P1489.D (0.05)

0

2

1

3

0

0

1

r1490

CO: Droop freq. [Hz]

0

Enable droop

0 ... 1

P1492.D (0)

r1538

r1539

r1538

r1539

r0079

r1508

r1482

r0063

r1170

*)

*) only active, if pre-control is enabled
(P1496 > 0)



1. Droop is applied as a frequency setpoint on each inverter.

The droop increases the slip via the negative feedback of the torque setpoint to the frequency setpoint.

In a steady-state an even load distribution can be achieved if the slip characteristics are identical.
-

P1488 > 0

-

P1489 > 0

-

P1492 = 1


2. Droop can act as a setpoint or limitation for a group of inverters (i.e. master-slave inverters)

By use of the master-slave inverter technique an even load distribution is achieved across the whole
application.

This is accomplished by setting the torque setpoint (r1490) on the master inverter which then controls
the frequency of the master inverter and all connected slave inverters.
-

P1488 > 0

-

P1489 > 0

-

P1492 = 0

Possible Settings:

0

Droop input disabled

1 Torque

setpoint

2 Speed

controller

output

3

Speed controller integral output

Index:

P1488[0] : 1st. Drive data set (DDS)
P1488[1] : 2nd. Drive data set (DDS)
P1488[2] : 3rd. Drive data set (DDS)

Dependency:

Droop scaling (P1489) must be > 0 for droop to be effective.