40 inverter parameters – Siemens 440 User Manual

Page 257

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

257

3.40 Inverter

parameters

P3900

End of quick commissioning

Min: 0

CStat:

C

Datatype: U16 Unit:

-

Def:

0

P-Group: QUICK

Active: first confirm

QuickComm.: Yes Max: 3

Performs calculations necessary for optimized motor operation.

After completion of calculation, P3900 and P0010 (parameter groups for commissioning) are automatically
reset to their original value 0.

Possible Settings:

0

No quick commissioning

1

Start quick commissioning with factory reset

2

Start quick commissioning

3

Start quick commissioning only for motor data

Dependency:

Changeable only when P0010 = 1 (quick commissioning)

Note:

P3900 = 1 :
When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick
commissioning", are retained; all other parameter changes, including the I/O settings, are lost. Motor
calculations are also performed.

P3900 = 2 :
When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning
menu "Quick commissioning" (P0010 = 1) are calculated. The I/O settings are also reset to default and the
motor calculations performed.

P3900 = 3 :
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick
commissioning with this setting saves time (for example, if only motor rating plate data have been changed).

Calculates a variety of motor parameters, overwriting previous values (see parameter P0340, setting P0340
= 1).

P3950

Access of hidden parameters

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: ALWAYS

Active: first confirm

QuickComm.: No

Max: 255

Accesses special parameters for development (expert only) and factory functionality (calibration parameter).

r3954[13] CM version and GUI ID

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: -

Max: -

Used to classify firmware (only for SIEMENS internal purposes).

Index:

r3954[0] : CM version (major release)
r3954[1] : CM version (minor release)
r3954[2] : CM version (baselevel or patch)
r3954[3] : GUI ID
r3954[4] : GUI ID
r3954[5] : GUI ID
r3954[6] : GUI ID
r3954[7] : GUI ID
r3954[8] : GUI ID
r3954[9] : GUI ID
r3954[10] : GUI ID
r3954[11] : GUI ID major release
r3954[12] : GUI ID minor release

Level

1

Level

4

Level

4

Advertising