Siemens 440 User Manual

Page 72

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

72

6SE6400-5BB00-0BP0

P0625[3]

Ambient motor temperature

Min: -40.0

CStat:

CUT

Datatype: Float Unit:

°C

Def:

20.0

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 80.0

Ambient temperature of motor. The parameter for the stator resistance P0350 and rotor resistance P0354
relate to the ambient temperature.

P0626

P0625

P0627 P0628

P0308

Thermal

motor

model

r0630

r0633

r0632

r0631

P0304 P0305 P0307

Equivalent

circuit

P0310 P0311

P1910

Index:

P0625[0] : 1st. Drive data set (DDS)
P0625[1] : 2nd. Drive data set (DDS)
P0625[2] : 3rd. Drive data set (DDS)

Note:

Following items should be considered when using P0625:
-

The ambient temperature has to be entered prior to motor data identification.

-

An accuracy of +/- 5°C is adequate.

-

The motor data identification should be carried out on a cold motor (ambient temperature = stator
temperature = rotor temperature).

-

The highest accuracy at temperature adaption of the stator resistance and rotor resistance can be
achieved by connecting a KTY84 sensor.

P0626[3]

Overtemperature stator iron

Min: 20.0

CStat:

CUT

Datatype: Float Unit:

°C

Def:

50.0

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 200.0

Overtemperature of stator iron.

Index:

P0626[0] : 1st. Drive data set (DDS)
P0626[1] : 2nd. Drive data set (DDS)
P0626[2] : 3rd. Drive data set (DDS)

Note:

See parameter P0627















Level

3

Level

4

Advertising